Loading...
HomeMy WebLinkAboutOrd 250-2006 Adopting 2005 International Fire Code with Amendments.pdfClTY OF ANNA, TEXAS ORDINANCE NO. 250-2006 AN ORDINANCE OF THE ClTY OF ANNA, TEXAS, ADOPTING THE 2003 EDITION OF THE INTERNATIONAL FlRE CODE; ADOPTING THE NORTH CENTRAL TEXAS COUNCIL OF GOVERNMENTS RECOMMENDED AMENDMENTS, AS AMENDED HEREIN; ADOPTING A SCHEDULE OF FEES; AUTHORIZING THE MAYOR OR HIS AUTHORIZED REPRESENTATIVE TO ENFORCE THE PROVISIONS OF THE INTERNATIONAL FlRE CODE; PROVIDING A REPEALER CLAUSE; PROVIDING A SAVINGS CLAUSE; AND PROVIDING FOR AN EFFECTIVE DATE WHEREAS, the City's existing fire code has determined the need for revising the City's existing lnternational Fire Code; and WHEREAS, the state had mandated that the lnternational Codes or comparable regulations are to be used if the City intends to regulate building construction; and WHEREAS, the other cities in the North Central Texas area have adopted or intend to adopt the lnternational Codes and the City Council desires that the City of Anna should have building standards comparable to other cities in the area; now therefore BE IT ORDAINED BY THE ClTY COUNCIL OF THE ClTY OF ANNA, TEXAS: Section 1. lnternational Fire Code adopted. The City Council hereby adopts the 2003 Edition of the lnternational Fire Code. Copies of the Code, and the amendments thereto, as referenced herein, are on file in the ofice of the city secretary for permanent record and inspection. The mayor, or his authorized representative, is hereby authorized and directed to enforce all provisions of the lnternational Fire Code, as adopted herein and as amended. Section 2. Amendments. The City Council hereby adopts the North Central Texas Council of Governments Recommended Amendments, (page 2, Section 202, High Rose Building. A building having any floors used for human occupancy located more than 55 feet (16.764 mm) above the lowest level of fire department vehicle access.) Option B. which are attached to this ordinance as Attachment A. Section 3. Inspection fees. The schedule of fees for various inspection and other services performed by the code enforcement official, as detailed in Attachment B, shall be paid to the city before any permit is issued. Section 4 Conflict and Repeal Clause Where, in a specific case, sections of the 2003 Edition of the International Fire Code-as adopted and amended by this Ordinance-specify requirements that conflict with requirements under other applicable sections of City of Anna Ordinances or adopted codes, the most restrictive sections shall govern. Otherwise, all parts of any other ordinance in conflict with the provisions of this ordinance are to the extent of such conflict hereby repealed. Section 5 Savinss Clause If any provision of this ordinance shall be held to be invalid or unconstitutional, the remainder of such ordinance shall continue in full force and effect the same as if such invalid or unconstitutional provision had never been a part hereof. Section 6 Effective Date This ordinance shall be effective upon the posting and/or publication of its caption as required by law and the City Secretary is hereby directed to implement such posting and/or publication. PASSED by the City Council of the City of Anna, Texas, this 10th day of January, 2006. AYE 6 NAY 0 ABSTAIN 0 ATTESTED: APPROVED: City $ecretary, Natha Wilkison , Mayor, Kenneth Pelham ATTACHMENT A Recommended Amendments to the 2003 lnternational Fire Code North Central Texas Council of Governments region The following sections, paragraphs, and sentences of the 2003 lnternational Fire Code are hereby amended as follows: Standard type is text from the IFC. Underlined type is text inserted. F A double asterisk at the beginning of a section identifies an amendment carried over from the 2000 edition of the code and a triple asterisk identifies a new amendment with the 2003 code. Note: Fire sprinkler code provisions for single-family dwellings and duplexes may be found in the lnternational Residential Code. **Section 102.4; change to read as follows: 102.4 Application of lwikhq other codes. The design and construction of new structures shall comply with this code, and other codes as ap~licable . . . Repairs, alterations and additions to existing structures shall comply with this code and the lnternational l%&wg Building Code. (Reason: Clarification of requirements and that the IFC also applies to new residential construction and the lnternational Existing Building Code is not recommended for adoption at this time.) **Section 102.6; change to read as follows: 102.6 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 45 and such codes, when specificallv adopted, and standards shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between the provisions of this code and the referenced standards, the provisions of this code shall apply. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as adopted. (Reason: Legal wording to recognize locally adopted codes and amendments adopted with referenced codes.) ***Section 202; amend definition of Fire Watch as follows: FIRE WATCH. A temporary measure intended to ensure continuous and systematic surveillance of a building or portion thereof by one or more qualified individuals or standby personnel when required bv the fire code official, for the purposes of identifying and controlling fire hazards, detecting early signs of unwanted fire, raising an alarm of fire and notifying the fire department. North Central Texas 1 March 2004 2003 IFC amendments 11 **Section 202; add a n read as follows: Option B **Section 202; add a new definition to read as follows: HIGH-RISE BUILDING. A buildinq havinq anv floors used for human occupancv located more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access. (Reason: To provide a definition that does not exist in the code.) **Section 202; add definitions as follows: SELF-SERVICE STORAGE FACILITY. Real property desiqned and used for the purDose of rentinq or leasinq individual storaqe spaces to customers for the purpose of storinq and removincl personal property on a self-service basis. STANDBY PERSONNEL. Qualified fire service personnel, approved bv the Fire Chief. When utilized, the number required shall be as directed by the Fire Chief. Charqes for utilization shall be as normally calculated by the iurisdiction. (Reason: To provide definitions that do not exist in the code.) **Section 307.2; change to read as follows: 307.2 Permit required. A permit shall be obtained from the fire code official in accordance with Section 105.6 prior to kindling a fire for recognized silvicultural or range or wildlife management practices, prevention or control of disease or pests, or open burninq a-bm%e. Application for such approval shall only be presented by and permits issued to the owner of the land upon which the fire is to be kindled. Examples of state or local law, or regulations referenced elsewhere in this section may include but not be limited to the followinq: 1. Texas commission on Environmental Quality quidelines andlor restrictions. 2. State, Countv or Local temporary or permanent bans on open burninq. 3. Local written policies as established by the Code Official. **Section 307.3; change to read as follows: 307.3 Location. The location for open burning shall not be less than &XI 300 feet (45-24Q 91 440 mm) from any structure, and provisions shall be made to prevent the fire from spreading to within &XI 300 feet (4524Q 91 440 mm) of any structure. (exceptions unchanged) North Central Texas 2 March 2004 2003 IFC amendments **Add Section 307.3.3 to read as follows: 307.3.3 Trench Burns. Trench burns shall be conducted in air curtain trenches and in accordance with Section 307.2. **Section 307.4; change to read as follows: 307.4 Attendance. Open burning, trench burns, bonfires or recreational fires shall be constantly attended until the . . . {remainder of section unchanged}. (Reason: Amendments to 307.2, 307.3, 307.3.3 and 307.4 better explain current requirements and recognize that jurisdictions have local established policies that best fit their environments.) **Section 308.3.1; change to read as follows: 308.3.1 Open-flame cooking devices. Charcoal burners and other open-flame cooking devices shall not be operated or located on combustible balconies or within 10 feet (3048 mm) of combustible construction. Exceptions: 1. One- and two-family dwellings. 2. Where buildings, balconies and decks are protected by an approved automatic sprinkler system. (Reason: To better explain protection options.) **Section 308.3. I. I; change to read as follows: 308.3.1.1 Liquefied-petroleumgas-fueled cooking devices. When permitted as listed in the exceptions of Section 308.3.1 ,LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction. Exception: One- and two-family dwellings, and other residential occupancies when those residential occupancies are in compliance with Section 308.3.1, exception #2, may have containers with a water capacity not areater than 20 pounds (9.08 ka) [nominal 1 pound (0.454 kq) LP-aas ca~acitvl. (Reason: Clarification and defines container size residences are allowed.) ***Section 405. I; change to read as follows: 405.1 General. Emergency evacuation drills complying with the provisions of this section shall be conducted in the occupancies listed in Se&bAW2 Table 405.2 or when required by the fire code official. Drills shall be designed in cooperation with the local authorities. (Reason: To correct the discrepancy between general and specific requirements.) North Central Texas 3 March 2004 2003 IFC amendments ***Section 408.5.4; change to read as follows: 408.5.4 Drill frequency. Emergency evacuation drills shall be conducted at least fix twelve times per year, twe four times per year on each shift. (Reason: Due to the turn over in staff, twelve drills per year are necessary for procedural familiarity. This amendment is in line with Table 405.2) **Section 503.1.1; add the following sentence to the first paragraph: Except for sinqle- or two-familv residences, the path of measurement shall be alona a minimum of a ten feet (1 0') wide unobstructed pathway around the external walls of the structure. (Reason: Recognizes that the hose lay provision can only be measured along a pathway that is wide enough for fire fighter access.) **Section 503.2.1; change to read as follows: 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 29 24 feet (- 7315mm), except for approved security gates in accordance with Section 503.6, and an - unobstructed vertical clearance of not less than I" 14 feet (4267 mm). Exception: Vertical clearance may be reduced, provided such reduction does not impair access bv fire apparatus and approved siqns are installed and maintained indicatinq the established vertical clearance when approved. **Section 503.2.2; change to read as follows: 503.2.2 Authority. The fire code official shall have the authority to require an increase in the minimum access widths and vertical clearances where they are inadequate for fire or rescue operations. (Reason: Amendments to 503.2.1 and 503.2.2 recognize that the equipment now used in fire fighting is increasing in size. The code already recognizes that larger dimensions may be required under Section 503.2.2. The amendments are to standardize the dimensions for this area. With the increase in fire apparatus size, this will allow for the passage of two fire apparatus during a fire or EMS emergency.) **Section 503.3; change to read as follows: 503.3 Marking. 0 Approved stripinq or, when allowed by the code officialL signs, or both, shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Signs ew&kes and stripinq shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility. 11 ) Stripinq - Fire apparatus access roads shall be marked by painted lines of red traffic paint six inches (6) in width to show the boundaries of the lane. The words "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" shall appear in four inch (4") white letters at 25 feet intervals on the red border markinqs alona both sides of the fire lanes. Where a curb is available, the strippinq shall be on the vertical face of the curb. North Central Texas 4 March 2004 2003 IFC amendments /2) Siqns - Siqns shall read "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" and shall be 12" wide and 18" hiqh. Siqns shall be painted on a white backqround with letters and borders in red, usinq not less than 2" letterinq. Siqns shall be permanently affixed to a stationary post and the bottom of the siqn shall be six feet, six inches (6'6") above finished qrade. Siqns shall be spaced not more than fifty feet (50') apart. Sians mav be installed on permanent buildings or walls or as approved by the Fire Chief. (Reason: Establishes a standard method of marking.) **Section 503.4; change to read as follows: 503.4 Obstruction of fire apparatus access roads. Fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles. The minimum widths and clearances established in Section 503.2.1 and anv area marked as a fire lane as described in Section 503.3 shall be maintained at all times. (Reason: As originally worded, it implied that vehicles could be parked in the marked fire lane and not be in violation if the minimum width is still maintained. Current accepted enforcement practice is to require all of the marked fire lane to be maintained clear and unobstructed.) **Section 704.1; change to read as follows: 704.1 Enclosure. Interior vertical shafts, including but not limited to stairways, elevator hoistways, service and utility shafts, that connect two or more stories of a building shall be enclosed or protected accordance with the codes in effect at the time of construction but, reqardless of when constructed, not less than as specified in Table 704.1. When openings are required to be . . . {remainder of section unchanged}. (Reason: Provides standard minimum protection retroactively, but clarifies that this section is not to be used to reduce higher protection levels that were required when originally constructed.) ** Section 803.3.2 and Section 803.4.2; add an exception to read as follows: Exception: Corridors protected bv an approved automatic sprinkler svstem installed in accordance with Section 903.3.1 .I shall be limited to 50 percent of the wall area. (Reason: This change allows an increase in wall coverage due to the presence of sprinklers.) **Section 804.1.1; add a second exception to read as follows: Exceptiong: 1. {existing exception unchanged} - 2. Trees shall not be prohibited inside private dwelling units of Group R-2 Occupancies. (Reason: Eliminates rule for private dwelling space.) North Central Texas 5 March 2004 2003 IFC amendments **Section 901.7; change to read as follows: 901.7 Systems out of service. Where a required fire protection system is out of service or in the event of an excessive number of activations, the fire department and the code official shall be notified immediately and, where required by the code official, the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. (Reason: Gives Fire Chief more discretion. Requires adoption of definition amendment in Section 202.) **Section 902.1; under "Standpipe, Types of' definition, amend "Manual dry" by adding a sentence to read as follows: The svstem must be supervised as specified in Section 905.2. (Reason: Corresponds with Section 905.2 recommended amendment.) --- -- - ***Section 903.2; delete the exception. (Reason: These areas pose a fire risk to the structural integrity of the building.) **Add Section 903.2.8.3 to read as follows: 903.2.8.3 Self-service storage facility. An automatic sprinkler svstem shall be installed throuqhout all self-service storaqe facilities. Exception: One-stow self-service storaqe facilities that have no interior corridors, with a one-hour fire barrier separation wall installed between every storaqe compartment. (Reason: Consistent with unamended IBC.) amend903.2.10.3andadd903.2.70.4, 903.2.10.5, and903.2.10.6 903.2.10.3 Build International Buildina Code, more above the lowest level North Central Texas 6 March 2004 2003 IFC amendments Option B **Section 903.2.10; amend 903.2.10.3 and add 903.2.10.4, 903.2.10.5, and 903.2.10.6 as follows: 903.2.10.3 Buildings more than 55 35 feet in height. An automatic sprinkler system shall be installed throughout buildings with a floor level, other than penthouses in compliance with Section 1509 of the lnternational Buildina Code, C that is located 5.5 2 feet (46764 10 668mm) or more above the lowest level of fire department vehicle access. - Exception: %Open parking structures in compliance with Section 406.3 of the International Buildinq Code. 903.2.10.4 High-Piled Combustible Storaqe. For any buildinq with a clear heiaht exceedinq 12 feet /4572 mm). see Chapter 23 to determine if those provisions apply. 903.2.10.5 Sprav Booths and Rooms. New and existinq spray booths and spravinn rooms shall be protected by an approved automatic fire-extinquishinq svstem. 903.2.10.6 Buildings Over 6,000 sq.ft. An automatic sprinkler svstem shall be installed throuqhout all buildinqs with a buildinq area over 6,000 sq.ft. For the purpose of this provision, fire walls shall not define separate buildinqs. Exceptions: 1. Open parkinq qaraqes in compliance with Section 406.3 of the lnternational Buildinq Code. 2. Type A-5. (Reason: Reflect local practices.) **Section 903.3.1.1.1; change to read as follows: 903.3.1.1.1 Exempt locations. When approved bv the code official. automatic lwtawtk sprinklers shall not be required in the following rooms or areas where such . . . {bulk of section unchanged} . . . because it is damp, of fire-resistance-rated construction or contains electrical equipment. 1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard. 2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the code official. 3. Generator and transformer rooms, under the direct control of a public utilitv, separated from the remainder of the building by walls and floorlceiling or rooflceiling assemblies having a fire- resistance rating of not less than 2 hours. 4- fi (~eason: Gives more discretion to code official. Protects locations where fire risks are poorly addressed.) North Central Texas 7 March 2004 2003 IFC amendments **Section 903.3.5; add a second paragraph to read as follows: Water sup~lv as required for such svstems shall be provided in conformance with the supplv requirements of the respective standards; however, everv fire protection svstem shall be desiqned with a 10 psi safety factor. (Reason: To define uniform safety factor.) **Section 903.4; add a second paragraph after the exceptions to read as follows: Sprinkler and standpipe svstem water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe svstems except for fire department hose connection valves shall be electricallv supervised to initiate a supervisorv siqnal at the central station upon tamperinq. (Reason: To avoid significant water losses. Consistent with amendment to IFC 905.9.) **Add Section 903.6.2 to read as follows: 903.6.2 S~rav booths and rooms. New and existinu sprav booths and sprav rooms shall be protected by an approved automatic fire-extinquishinq system in accordance with Section 1504. (Reason: Consistent with amendment to IFC 1504.) **Section 905.2; change to read as follows: 905.2 Installation standards. Standpipe systems shall be installed in accordance with this section and NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 psia and a maximum of 40 psiq air pressure with a hiqhllow alarm. (Reason: To define manual dry standpipe supervision requirements.) **Section 905.3.2; delete exceptions #I and #2. (Reason: Reflects local practice.) **Section 905.4, item #5; change to read as follows: 5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope), each standpipe shall be provided with a two-way hose connection located either. . . {remainder of paragraph unchanged}. . . (Reason: Clarity.) **Section 905.9; add a second paragraph after the exceptions to read as follows: North Central Texas 2003 IFC amendments 8 March 2004 Sprinkler and standpipe svstem water-flow detectors shall be provided for each floor tap to the sprinkler svstem and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electricallv supervised to initiate a supervisory siqnal at the central station upon tamperinq. (Reason: To avoid significant water losses. Consistent with amendment to IFC 903.4.) **Add Section 907.1.3 to read as follows: 907.1.3 Desian Standards. All alarm svstems new or replacement servinq 50 or more alarm actuatinq devices shall be addressable fire detection svstems. Alarm svstems servinq more than 75 smoke detectors or more than 200 total alarm activatinq devices shall be analoq intelliqent addressable fire detection svstems. Exception: Existinq svstems need not complv unless the total buildinq remodel or expansion initiated after the effective date of this code, as adopted, exceeds 30% of the buildinq. When cumulative buildinq remodel or expansion exceeds 50% of the buildinq must comply within 18 months of permit application. (Reason: Consistent with local practice.) **Section 907.2.3; change to read as follows: 907.2.3 Group E. A manual fire alarm system shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. An approved smoke detection svstem shall be installed in Group E day care occupancies. Unless separated by a minimum of 100' open space, all buildinqs, whether portable buildinqs or the main buildinq, will be considered one buildina for alarm occupant load consideration and interconnection of alarm svstems. (Reason: To distinguish educational from day care occupancy minimum protection requirements. Further, to define threshold at which portable buildings are considered a separate building for the purposes of alarm systems.) **Section 907.2.3; change exception #I and add exception #1.1 to read as follows: 1. Group E educational and dav care occupancies with an occupant load of less than 50 when provided with an approved automatic sprinkler svstem. 1 .I. Residential In-Home dav care with not more than 12 children mav use interconnected sinqle station detectors in all habitable rooms. (For care of more than five children 2 112 or less vears of aqe, see Section 907.2.6.) (Reason: Consistent with Texas State laws concerning day care facility requirements.) North Central Texas 2003 IFC amendments 9 March 2004 I **Section 907.2.12; change to read as follows: 907.2.12 High-rise buildings. Buildings having any floors used for human occupancy located more than 75 55 feet (ZUM3 16 764 mm) above the lowest level of fire department vehicle access shall be provided with an automatic fire alarm system and an emergency voicelalarm communications system in accordance with Section 907.2.12.2. (Reason: To correct definition of high-rise for Option B jurisdictions.) **Section 907.2.12, exception #3; change to read as follows: 3. Buildings with an occupancy in Group A-5 in accordance with Section 303.1 of the International Building Code, when used for open air seatinq; however, this exception does not apply to accessow uses includinq but not limited to sky boxes, restaurants and similarly enclosed areas. (Reason: To indicate that enclosed areas within open air seating type occupancies are not excepted from automatic fire alarm system requirements.) -- **Section 907.4; add a second paragraph to read as follows: Manual alarm actuatinq devices shall be an approved double action tvpe. (Reason: Consistent with local requirements.) **Add Section 907.6.1 to read as follows: 907.6.1 Installation. All fire alarm systems shall be installed in such a manner that the failure of any sinqle alarm-actuatina or alarm-indicatinq device will not interfere with the normal operation of any other such devices. All systems shall be Class "A wired with a minimum of six feet separation between supply and return loops. IDC - Class "A" style - D - SLC Class "A Style 6 - notification Class "B" Style Y. (Reason: To provide uniformity in system specifications and guidance to design engineers.) ore than 75 feet (22 860 mm) North Central Texas 10 March 2004 2003 IFC amendments Option B **Section 907.9.2; change to read as follows: 907.9.2 High-rise buildings. In buildings that have anv floor located more than 75 55 feet (Z%€% 16 764 mm) above the . . . {remainder of section unchanged}. (Reason: Correct definition of high-rise for Option B jurisdictions.) ***Section 1008.1.3.4; add criteria #7 as follows: 7. If a full buildinq smoke detection svstem is not provided. approved smoke detectors shall be provided on both the access and eqress sides of doors and in a location approved bv the authoritv havinq jurisdiction of NFPA 72. Actuation of a smoke detector shall automaticallv unlock the door. (Reason: To increase safety by preventing smoke from causing a malfunction in the motion sensor release mechanism while at the same time obscuring the manual release button and thereby potentially trapping people in an exit corridor of a burning building.) **Section 1016.1; add an exception #5 to read as follows: 5. In Group B office buildings, corridor walls and ceilinqs need not be of fire-resistive construction within office spaces of a single tenant when the space is equipped with an approved automatic smoke-detection svstem within the corridor. The actuation of anv detector shall activate alarms audible in all areas served by the corridor. The smoke-detection svstem shall be connected to the buildinq's fire alarm svstem where such a svstem is ~rovided. (Reason: Consistent with regional amendment to IBC 1016.1 .) Option B **Section 1019.1.8; change to read as follows: 1019.1.8 Smokeproof enclosures. In buildings required to comply with Section 403 or 405, each of the exits of a building that serves stories where Kte any floor surface is located more than 75 55 feet (2246O 16 764 mm) above the lowest level of fire . . . {remainder of section unchanged}. North Central Texas 2003 IFC amendments 11 March 2004 (Reason: Correct definition of high-rise for Option B jurisdictions.) **Section 1504.6; change to read as follows: 1504.6 Fire Protection. New and existinq sprav Spay booths and spray rooms shall be protected by an approved automatic fire-extinguishing system . . . [remainder of section unchanged} . . . (Reason: Consistent protection in all spray booths.) - ph to the definition of "HI I Option B **Section 2302; add a second paragraph to the definition of "High-Piled Combustible Storage" to read as follows: I Anv buildins exceedinq 6,000 sa.ft. that has a clear heiqht in excess of 12 feet, makinq it possible to be used for storase in excess of 12 feet, shall be considered to be hiqh-piled storaqe and shall complv with the provisions of this section. When a specific product cannot be identified, a fire protection system shall be installed as for Class IV commodities, to the maximum pile heiqht. (Reason: To provide protection for worst-case scenario in flexible or unknown situations.) **Section 3301.1.3; change to read as follows: 3301.1.3 Fireworks. The possession, manufacture, storage, sale, handling and use of fireworks are prohibited. Exceptions: 1. Only when approved for fireworks displavs, storage and handling of fireworks as provided ptwwtkd in Section 3304 and 3308. 2. 0 &The use of fireworks for approved display as permitted in Section 3308. (Reason: Restricts to approved displays, which is consistent with local practice.) ***Section 3302; change the definition of "fireworks" to read as follows: North Central Texas 12 March 2004 2003 IFC amendments FIREWORKS. Any composition or device for the purpose of producing a visible or an audible effect for entertainment purposes by combustion, deflagration, aREl detonation, andlor activated by ignition with a match or other heat producina device that meets the definition of 1.4G fireworks or 1.3G fireworks as set forth herein. (Reason: lncreased safety from fireworks related injuries.) **Section 3403.6; add a sentence to read as follows: An approved method of secondarv containment shall be provided for underqround tank and piping systems. **Section 3404.2.11.5; add a sentence to read as follows: An approved method of secondarv containment shall be provided for underqround tank and pipinq systems. (Reason: lncreased protection in response to underground leak problems and rehabilitation difficulty in underground applications.) **Section 3404.2.11.5.2; change to read as follows: 3404.2.1 1.5.2 Leak detection. Underground storage tank systems . . . [bulk of provision unchanged} . .. and installed in accordance with NFPA 30 and as specified in Section 3404.2.1 1.5.3. (Reason: Reference to Section 3404.2.1 1.5.3 amendment.) **Add Section 3404.2.11.5.3 to read as follows: 3404.2.11.5.3 Dry sumps. Approved samplinq tubes of a minimum 6 inches in diameter shall be installed in the backfill material of each underqround flammable or combustible liquid storaae tank. The tubes shall extend from a point 12 inches below the averaqe grade of the excavation to qround level and shall be provided with suitable surface access caps. Each tank site shall provide a samplinq sump at the corners of the excavation with a minimum of 4 sumps. Sampling tubes shall be placed in the product line excavation within 10 feet of the tank excavation and one everv 50 feet routed alonq product lines towards the dispensers, a minimum of two are required. (Reason: Provides an economical means of checking potential leaks at each tank site.) **Delete Section 3406.5.4.5 and replace with the following: 3406.5.4.5 Commercial, industrial, clovernmental or manufacturinq. Dis~ensinq of Class II and Ill motor vehicle fuel from tank vehicles into the fuel tanks of motor vehicles located at commercial, industrial, qovernmental or manufacturinq establishments is allowed where permitted, provided such dis~ensinq operations are conducted in accordance with Sections 3406.5.4.5.1 throuqh 3406.5.4.5.3. 3406.5.4.5.1 Site requirements. 1. Dispensinq may occur at sites that have been permitted to conduct mobile fueling. North Central Texas 13 March 2004 2003 IFC amendments 2. A detailed site plan shall be submitted with each application for a permit. The site plan must indicate: a. all buildinqs, structures, and appurtenances on site and their use or function; b. all uses adiacent to the property lines of the site; c. the locations of all storm drain openings. adiacent waterways or wetlands; d. information reqardinq slope, natural drainaqe, curbinq, impoundinq and how a spill will be retained upon the site property; and, e. The scale of the site plan. 3. The Code Official is authorized to impose limits upon: the times and/or days during which mobile fueling operations are allowed to take place and specific locations on a site where fuelinq is permitted. 4. Mobile fuelinq operations shall be conducted in areas not qenerallv accessible to the public. 5. Mobile fuelinq shall not take place within 15 feet (4.572 m) of buildinqs. property lines. or combustible storaqe. 3406.5.4.5.2 Refuelinq Operator Requirements. 1. The owner of a mobile fuelinq operations shall provide to the iurisdiction a written response plan which demonstrates readiness to respond to a fuel spill. carrv out appropriate mitigation measures, and to indicate its process to properly dispose of contaminated materials when circumstances require. 2. The tank vehicle shall comply with the requirements of NFPA 385 and Local, State and Federal requirements. The tank vehicle's specific functions shall include that of supplyinq fuel to motor vehicle fuel tanks. The vehicle and all its equipment shall be maintained in qood repair. 3. Siqns prohibitinq smokinq or open flames within 25 feet (7.62 m) of the tank vehicle or the point of fuelinq shall be prominentlv posted on 3 sides of the vehicle includino the back and both sides. 4. A fire extinquisher with a minimum ratinq of 40:BC shall be provided on the vehicle with siqnaqe clearly indicatinq its location. 5. The dispensinq nozzles and hoses shall be of an approved and listed type. 6. The dispensinq hose shall not be extended from the reel more than 100 feet (30.48m) in lenqth. 7. Absorbent materials, non-water absorbent pads, a 10 foot (3.048 m) lonq containment boom. an approved container with lid, and a non-metallic shovel shall be provided to mitiqate a minimum 5- gallon fuel spill. 8. Tanker vehicles shall be equipped with a fuel limit switch such as a count-back switch, limitinq the amount of a sinqle fuelinq operation to a maximum of 500 qallons (1 893 L) between resettinqs of the limit switch. Exception: Tankers utilizinq remote emerqencv shut-off device capabilitv where the operator constantly carries the shut-off device which, when activated, immediately causes flow of fuel from the tanker to cease. 9. Persons responsible for dispensinq operations shall be trained in the appropriate mitiqatinq actions in the event of a fire, leak, or spill. Traininq records shall be maintained by the dispensinq company and shall be made available to the Code Official upon request. 10. Operators of tank vehicles used for mobile fueling operations shall have in their possession at all times an emergency communications device to notify the proper authorities in the event of an emerqencv. 3406.5.4.5.3 Operational Requirements. 1. The tank vehicle dispensincl equipment shall be constantlv attended and operated onlv bv desiqnated personnel who are trained to handle and dispense motor fuels. 2. Prior to beqinninq dispensing operations, precautions shall be taken to assure ignition sources are not present. 3. The engines of vehicles being fueled shall be shut off durinq dispensing operations. 4. Night time fuelinq operations shall onlv take place in adequately liqhted areas. North Central Texas 14 March 2004 2003 IFC amendments 5. The tank vehicle shall be positioned with respect to vehicles beinq fueled so as to preclude traffic from drivinq over the delivew hose and between the tank vehicle and the motor vehicle beinq fueled. 6. Durinq fuelinq operations, tank vehicle brakes shall be set, chock blocks shall be in place and warninq liqhts shall be in operation. 7. Motor vehicle fuel tanks shall not be topped off. 8. The dispensinq hose shall be properlv placed on an approved reel or in an approved comoartment prior to movinq the tank vehicle. 9. The Code Official and other appropriate authorities shall be notified when a reportable spill or unauthorized discharqe occurs. (Reason: Provides clarity and organization of the site, operation and use requirements.) **Add Section 3803.2.1.8 to read as follows: 3803.2.1.8 Jewelrv Repair, Dental Labs and Similar Occupancies. Where natural gas service is not available, portable LP-Gas containers are allowed to be used to supplv approved torch assemblies or similar appliances. Such containers shall not exceed 20-pound (9.0 kq) water capacity. Aqqreqate capacity shall not exceed 60-pound (27.2 kq) water capacity. Each device shall be separated from other containers by a distance of not less than 20 feet. (Reason: To provide a consistent and reasonable means of regulating the use of portable LP-Gas containers in these situations.) **Section 3804.2; add an exception #2 to read as follows: Exceptions: 1. {existing exception unchanged} - 2. Except as permitted in 308.3 and 3804.3.2. LP-gas containers are not permitted in residential areas. (Reason: To provide a consistent and reasonable means of regulating the use of portable LP-Gas containers. References regional amendment to IFC 3804.3.2.) **Add Section 3804.3.2 to read as follows: 3804.3.2 Spas. Pool Heaters and other listed devices. Where natural qas service is not available. LP- Gas containers are allowed to be used to supplv spa and pool heaters or other listed devices. Such containers shall not exceed 250-qallon water capacitv. See Table 3804.3 for location of containers. (Reason: Allows for an alternate fuel source.) END North Central Texas 15 March 2004 2003 IFC amendments ATTACHMENT B FEE SCHEBmES FOR PROJECTS: These fees may be assessed with the application submittal: BUILDING .PERMIT FEE. BUILDING AND MEP PLAN REVIEW FEE. FIRE.PLAN REVTEW FEE. PLUMBING FEE MECHANICAL FEE. ELECTRICAL FEE. HEALTH FEE (IF MPkIClaBLE). METER FEE & SANITARY SEWER FEES. IMPACT FEE. $7.50 per $1000 valuation of work. Minimum $20.00. BhTHkDlll?TG AND MIEP PLAN WIEmW FEE: $.07 per square foot of building area. S.02 per square foot of building area ranging from 0-100,000 square feet. For buildings over 100,000 square feet, please refer to fee schedules. BdEC-GWL, IELECTNCA&, AND PLWING FEES: These fees are calculated by square footage of floor area. 1-3,000 square feet $60.00 3,001 -1 0,000 square feet $80.00 10,001-50,000 square feet $100.00 50,001-1 00,000 square feet $125.00 over 100,000 square feet $150.00 Fees are separate (i.e. $60.00 plumbing, $60.00 electrical, $60.00 mechanical. -Earn PLAN I3EVIEW FEE: $250.00 (If applicable to requirements.) METER & SEWER FEES: Please contact the City of Anna Public Works Department for meter and sanitary sewer sizes. Verify that water and sewer taps exist on site. Fees will be paid to the City of Anna Building Inspection Department. lJdPACT FEES: Please contact the City of Anna Building Inspection Department for all Impact fees. Fees dl be paid to the City of h a Building Inspection Department. When submitting application for Shell only permit, include only shell valuation. When building has more than one floor, separate permits per floor is required. This fee calculation is provided for information only. Tine City of Anna Building Inspections Department will calculate and assess all fees.