Loading...
HomeMy WebLinkAboutOrd 373-2008 Adopting the 2006 IFC and Appendix B-G.pdfCITY OF ANNA, TEXAS ORDINANCE NO. 3M2008 AN ORDINANCE OF THE CITY OF ANNA, TEXAS, ADOPTING THE 2006 EDITION OF THE INTERNATIONAL FIRE CODE; ADOPTING APPENDIX S -G OF THE INTERNATIONAL FIRE CODE; ADOPTING THE NORTH CENTRAL TEXAS COUNCIL OF GOVERNMENTS RECOMMENDED AMENDMENTS, AS AMENDED HEREIN; ADOPTING A SCHEDULE OF FEES; AUTHORIZING THE MAYOR OR HIS AUTHORIZED REPRESENTATIVE TO ENFORCE THE PROVISIONS OF THE INTERNATIONAL FIRE CODE; PROVIDING A REPEALER CLAUSE; PROVIDING A SAVINGS CLAUSE; AND PROVIDING FOR AN EFFECTIVE DATE WHEREAS, the City's existing fire code has determined the need for revising the City's existing International Fire Code; and WHEREAS, the state had mandated that the International Codes or comparable regulations are to be used if the City intends to regulate building construction; and WHEREAS, the other cities in the North Central Texas area have adopted or intend to adopt the International Codes and the city council desires that the City of Anna should have building standards comparable to other cities in the area; now therefore BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF ANNA, TEXAS: Section 1. International Fire Code adopted. The city council hereby adopts the 2006 Edition of the International Fire Code including Appendix Chapters B C. D. E, F and G. Copies of the Code, and the amendments thereto, as referenced herein, are on file in the office of the city secretary for permanent record and inspection. The mayor, or his authorized representative, is hereby authorized and directed to enforce all provisions of the International Fire Code, as adopted herein and as amended. Section 2. Amendments. The city council hereby adopts the North Central Texas Council of Governments Recommended Amendments, which are attached to this ordinance as Attachment A. OM No. 373-2008 Adopting the 20061FC.doc 1 04-08-08 Section 3. Inspection fees. The schedule of fees for various inspection and other services performed by the code enforcement official, as detailed in Attachment B, shall be paid to the city before any permit is issued. Section 4 Repeal Clause All parts of any ordinance in conflict with the provisions of this ordinance are to the extent of such conflict hereby repealed. Section 5 Savinas Ciause If any provision of this ordinance shall be held to be invalid or unconstitutional, the remainder of such ordinance shall continue in full force and effect the same as if such invalid or unconstitutional provision had never been a part hereof. Section 6 Effective bate This ordinance shall be effective upon the posting and/or publication of its caption as required by law and the City Secretary is hereby directed to implement such posting and/or publication. PASSED by the City Council of the City of Anna, Texas, this 6th day of April, 2008, AYE 6 NAY 0 ABSTAIN 0 ATTESTED: APPROVED: City ecretary, Natha Wilkison Mayor, Kenneth Pelham _0f oonwiw,n„iii, OF An.'",. n Ord No. 373-2008 Adopting the 2006 IFC.dDc 2 04-MO8 ATTACHMENTA Recommended Amendments to the 2006 International Fire Code North Central Texas Council of Governments region The following sections, paragraphs, and sentences of the 2006 International Fire Code are hereby amended as follows: Standard type is text from the IFC. Underlined type is text inserted. Lined -through type is deleted text from IFG4 A double asterisk at the beginning of a section identifies an amendment carried over from the 2003 edition of the code and a triple asterisk identifies a new or revised amendment with the 2006 code. Explanation of Options A and B: Please note that as there is a wide range in fire fighting philosophies I capabilities of cities across the region, OPTION A" and OPTION "B" are provided in the Fire and Building Code amendments. Jurisdictions should choose one or the other based on their fighting philosophies I capabilities when adopting code amendments. Note: Fire sprinkler code provisions for single-family dwellings and duplexes may be found in the International Residential Code. "`Section 102.1; add #5: 102.1 Construction and design provisions. 5. The provisions of this code apply to buildings built under the IRC and IBC. (Reason To clarify that the fire safety provisions of the fire code do apply to all construction.) **Section 102.4; change to read as follows: 102.4 Application of buildingto her codes. The design and construction of new structures shall comply with this code, and other codes as applicable the -Inte mationat-Baildirg Code, and any alterations, additions, changes in use or changes in structures required by this code, which are within the scope of the international Building Code, shall be made in accordance therewith. (Reason: Clarification of requirements and that the IFC also applies to new residential construction.) "Section 102.6; change to read as follows: 102.6 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 45 and such codes. when specificaiiv adopted, and standards shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between the provisions of this code and the referenced standards, the provisions of this code shall apply. Whenever amendments have been adopted to the referenced. codes and standards. (Reason: To be consistent with the State of Texas, other referenced codes must be specifically adopted.) North Central Texas 1 September 2007 20061FC Amendments —Section 106.2; add Sections 106.2.1 and 106.2.2 as follows: (Reason: Clarifies that it is the permit holder's responsibility to notify the fire code official when the installation is ready for appropriate inspection and before covering up any work.) "Section 202; amend definition of Fire Watch as follows: FIRE WATCH. A temporary measure intended to ensure continuous and systematic surveillance of a building or portion thereof by one or more qualified individuals or standby Personnel when required by the fire code official for the purposes of identifying and controlling fire hazards, detecting early signs of unwanted fire, raising an alarm of fire and notifying the fire department. (Reason: Clearly defines options to the fire department for providing a fire watch.) Option A **Section 202; add a new definition to read as follows: HIGH-RISE BUILDING. A building having any floors used for human occupancy located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access. Option B '*Section 202; add a new definition to read as follows: HIGH-RISE BUILDING. A building having any floors used for human occupancy located more than 55 feet (t 6 764 mm) above the lowest level of fire department vehicle access. (Reason: To provide a definition that does not exist in the code.) North Central Texas 2 September 2007 2006 IFC Amendments "'Section 202; add definitions as follows: SELF-SERVICE STORAGE FACILITY. Real property designed and used for the purpose of renting or leasing individual storage spaces to customers for the purpose of storing and removing personal property on a self-service basis. (Reason: To provide definitions that do not exist in the code.) *`Section 307.2; change to read as follows 307.2 Permit required. A permit shall be obtained from the fire code official in accordance with Section 105.6 prior to kindling a fire for recognized sitvicuitural or range or wildlife management practices, prevention or control of disease or pests, or open burring a-benfire. Application for such approval shall only be presented by and permits issued to the owner of the land upon which the fire is to be kindled. Examples of state or local law or regulations referenced elsewhere in this section may include but not be limited to the following: 1. Texas Commission on Environmental Quality guidelines and/or restrictions. 2. State County or Local temporary or permanent bans on open burning 3. Local written policies as established by the Code Official. "Section 307.4; change to read as follows; 307.4 Location. The location for open buming shall not be less than 60 300 feet (45-249 91 440 mm) from any structure, and provisions shall be made to prevent the fire from spreading to within 50 300 feet (46240 91 440 mm) of any structure. (exceptions unchanged) Add Section 307.4.3 to read as follows: 307.4.3 Trench Burns. Trench bums shall be conducted in air curtain trenches and in accordance with Section 307.2. **Section 307.5; change to read as follows: North Central Texas 3 September 2007 2006 IFC Amendments 307.5 Attendance. Open burning, trench burns, bonfires or recreational Ores shall be constantly attended until the ... (remainder of section unchanged). (Reason: Amendments to 307.2, 307.4, 307.4.3 and 307.5 better explain current requirements and recognize thatjurisi ictions have local established policies that best fit their environments) —Section 308.3.1; change to read as follows: 308.3.1 Open -flame cooking and heating devices. Open -flame cooking on COmbusdbie balconies rle,_�ks Or Exceptions: 1. One- and two-family dwellings. 2. Where buildings, balconies and decks are protected by an approved automatic sprinkler system. (Reason: Decrease fire risk in multi -family dwellings and minimizes ignition sources) --Section 308.3.1.1; Amended to add the following exceptions: Exceptions: 1. One- and two-family dwellings may have containers with a water capacity not -greater than 20 pounds (9.08 kg) (nominal 8 pound 13.632 kg) LP -gas capacity) with an imorimate capacity not to exceed 1001 s (5 containers). 2 Other residential occupancies where buildings, balconies and decks are protected by an (Reason: 7o clarify allowable limits for 1 & 2 family dwellings, and allow an expansion for sprinklemd multi -family uses. Clarification and defines container size residences are allowed.) —Section 401.3; add Section 401.3.4 as follows: 401.3.4 Fire Alarms and Nuisance Alarms. False alarms and nuisance alarms shall not be given, signaled or transmitted or caused or permitted to be given, signaled or transmitted in any manner. (Reason: Places the responsibility of the business or property owner to maintain their fire alarm systems in approved condition. Allows the enforcement of prohibition of false alarms' Replaces language lost from the 1997 Code) North Central Texas 4 September 2007 2006 IFC Amendments "Section 503.1.1; add the following sentence to the first paragraph: Except for sinale- or two-family residences the oath of measurement shall be along a minimum of a ten feet (109 wide unobstmcted pathway around the external walls of the structure. (Reason: Recognizes that the hose lay provision can only be measured along a pathway that is wide enough for fire fighter access.) "Section 503.2.1; change to read as follows: 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 24 feet (6096mm7315mm , except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 43-feet4minches-445 mm.4 14 feet (4267 mm). -Section 503.2.2; change to read as follows: 503.2.2 Authority. The fire code official shall have the authority to require an increase in the minimum access widths and vertical clearances where they are inadequate for fire or rescue operations. (Reason: Amendments to 503.2.1 and 503.2.2 recognize that the equipment now used in fire fighting is increasing in size. The code already recognizes that larger dimensions maybe required under Section 503.2.2. The amendments are to standardize the dimensions for this area. With the increase in fire apparatus size, this will allow for the passage of two fire apparatus during a fire or EMS emergency.) **Section 503.3; change to read as follows: 503.3 Marking. Striping signs or other markings when approved by the code official shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Striping, signs and other markings shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility. (Reason: Establishes a standard method of marking.) North Central Texas 5 September 2007 2006 IFC Amendments —Section 503.4; change to read as follows; 503.4 Obstruction of fire apparatus access roads. Fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles. The minimum widths and clearances established in Section 503.2.1 and any area marked as a fire lane as described in Section 503.3 shall be maintained at all times. (Reason: As originally worded, it implied that vehicles could be parked in the marked fire lane and not be in violation if the minimum width is stili maintained. Current accepted enforcement practice is to require all of the marked fire lane to be maintained clear and unobstructed.) "'Section 505.1; replace to read as follows: 505.1 Address Address numbers shall be Arabic numerals or alphabet letters. The minimum stroke width shall be 0.5 inches. (Reason: To increase the minimum requirements for commercial and establish a minimum for single- family residential.) —Add Section 511 Emergency Radio Communications to read as follows: SECTION 511 EMERGENCY RADIO COMMUNICATIONS emergency radio system's Provider and system manages (Reason: Ensure proper communication inside the building during emergency operations.) North Central Texas 6 September 2007 2006 IFC Amendments "Section 704. t; change to read as follows 704.1 Enclosure. Interior vertical shafts, including but not limited to stairways, elevator hoistways, service and utility shafts, that connect two or more stories of a building shall be enclosed or protected in accordance with the codes in effect at the time of construction but, reaardiess of when constructed, not less than as specified in Table 704.1. (Reason: Provides standard minimum protection retroactively, but clarifies that this section is not to be used to reduce higher protection levels that were required when originally constructed) — Section 807.4.3.2 and Section 807.4.4.2; add an exception to read as follows: Exception: Corridors Protected by an approved automaticsprinkler system installed in accordance with Section 903.3.1.1 shall be limited to 50 percent of the wall area. (Reason: This change allows an increase in wall coverage due to the presence of sprinklers.) "*Section 901.6,1; add section to read as follows 601.6.1.1 Standoioe Testina. Building ownersimanaaers must utilize a licensed fire protection contractor to test and certiry standpipe systems In addition to the testing and maintenance requirements of NFPA 25 applying to standpipe systems, the following additional requirements shall be applied to the testing that is required every 5 Years: 1. The piping between the Fire Department Connection (FDC) and the standpipe shall be hydrostatically tested for all FDC's on any type of standpipe system Hydrostatic testing shall also be conducted in accordance with NFPA 25 requirements for the different types of standpipe systems. 2. 3. Any Pressure relief, reducing, r control valves shall be tested in accordance with the reguirements, of NFPA 25. 4. If the FDC is not already Provided with approved ceps. the contractor shall install such caps for all FDC's. Contact the Fire Marshal for additional information. 5. 6. The contractor shall follow the procedures as required b "Texas Administrative Code Tide 28. Insurance, Part I. Texas Department of Insurance, Chapter 34. State Fire Marshal, Subchapter G. North Central Texas 7 September 2007 2006 IFC Amendments 7. Additionally, records of the testing shall be maintained by the owner and contractor, as required by the State Rules mentioned above and NFPA 25. B. Standpipe system tests where water will be flowed external to the building shall not be conducted during freezing conditions or during the day prior to expected night time freezing conditions. (Reason: Increases the reliability of fire protection system and re-emphasizes the requirements of NFPA 25.) "'Section 901.7; amend to read as follows: 901.7 Systems out of service. Where a required fire protection system is out of service or in the event of an excessive number of activations, the fire department and the code official shall be notified immediately and, where required by the code official, the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. (Reason: Gives Fire Chief mom discretion. Requires adoption of definition amendment in Section 202.) -Section 903.2; delete the exception. (Reason: These areas pose a fire risk to the stmctural integrity of the building.) "Add Section 903.2.8.3 to read as follows: 903.2.8.3 Self-senticii storage facility. An automaticsprinkler system shall be installed throughout all self-service storage facilities. Exception: One-story self-service storage facilities that have no interior corridors with a one- hour fire barrier separation wall installed between every stereos compartment (Reason: Fire departments are unable to inspect these commercial occupancies and am unaware of the contents being stored.) "—Amend the title of Section 903.2.10 to read 'Windowless stories in a8 occupancies except R-3 and U". (Reason: Current fide of windowless stories in all occupancies does not cimently cover all the subsections listed and referenced. North Central Texas 8 September 2007 2006 IFC Amendments Option A —Section 903.2.10; amend 903.2.10.3 and add 903.2.10.4, 903.2.10.5, and 903.2.10.6 as follows: 903.2.10.3 Buildings more than 55 feet in height. An automatic sprinkler system shall be installed throughout buildings with a floor level other than penthouses in corn liance with Section 1509 of the International Building Code, that is located 55 feet (16 764 mm) or more above the lowest level of fire department vehicle access. Exception: 1. Airpent Vis. 2—Open parking structures in compliance with Section 406.3 of the Building Code, 903.2.10.4 Hi h Piled Combustible Stora e. For any building with a clear height exceeding 12 feet (4572 mm), see Chapter 23 to determine if those provisions apply. 903.2.10.5 Spray Booths and Rooms. New and exisfinQ spray booths andspraying rooms shall be protected by an approved automatic fire -extinguishing system. Option B *'Section 903.2.10; amend 903.2.10.3 and add 903.2.10.4, 903.2.10.5, and 903.2.10.6 as follows: 903.2.10.3 Buildings more than 65 35 feet in height. An automatic sprinkler system shall be installed throughout buildings with a floor level. -other than Penthouses in compliance with Section 1509 of the International Building Code, that is located 55 35 feet (-1676410 668mm) or more above the lowest level of fire department vehicle access. Exception: 1--Airpert+eontrel-fewers+ 2—Open parking structures in compliance with Section 406.3 of the international BuildingCode. 3. Occupancies in Group F-2- 903.2.10.4 Hi h Piled Combustible Storage. For any building with a clear height exceeding 12 feet (4572 mm) see Chapter 23 to determine if those Provisions aooly. 903.2.10.5 Spray Booths and Rooms. New and existing spray booths and soraving rooms shall be protected by an approved automatic fire extin uishin system. 903.2.10.6 Buildings Over 6,000 sq.ft An automaticsprinkler system shall be installed throughout all buildings with a building area over 6,000 s .ft. For the Purpose of this Provision, fire walls shall not define separate buildings. Exceptions: 1. Open Parking garages in compliance with Section 406.3 of the international Building Code. 2. Type A-5. (Reason: Reflect local practices.) -*Section 903.3.1.1.1; change to read as follows: North Central Texas 9 September 2007 2006 IFC Amendments 903.3.1.1,1 Exempt locations. When approved by the code official automatic Automatic sprinklers shall not be required in the following rooms or areas where such ... {bulk of section unchanged) ... because it is damp, of fire -resistance -rated construction or contains electrical equipment. 1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard. 2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the code official. 3. Generator and transformer rooms under the direct control of a public utility, separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire - resistance rating of not less than 2 hours. 4 . (Reason: Gives more discretion to code official. Protects locations where fire risks are poorly addressed.) **Section 903.3.5; add a second paragraph to read as follows: (Reason: To define uniform safety factor.) `*Section 903.4; add a second paragraph after the exceptions to read as follows: (Reason: To avoid significant water losses. Consistent with amendment to IFC 905.9.) ***Section 903.4.2; add second paragraph to read as follows: The alarm device required on the exterior of the building shall be a weatherproof horn/strobe notification appliance with a minimum 75 candela strobe rating, installed as close as practicable to the fire department connection. (Reason: Fire department connections are not always located at the riser this allows the fire department faster access.) **Add Section 903.6.2 to read as follows: 903.6.2 Spray booths and rooms. New and existing spray booths and spray rooms shall be protected by an approved automatic fire -extinguishing system in accordance with Section 1504. North Central Texas 10 September 2007 20061FC Amendments (Reason: Consistent with amendment to IFC 1504.) "Section 905.2; change to read as follows: 905.2 Installation standards. Standpipe systems shall be installed in accordance with this section and NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 Osla and a. maximu (Reason: To define manual dry standpipe supervision requirements.) ' Add Section 905.3.8 and exception to read as follows: access. Exception: Automatic dry and semi-automatic dry standpipes are allowed as Provided for in NFPA 14. (Reason: Allows for the rapid deployment of hoselines to the body of the fire.) —Section 905.4, Item #5; change to read as follows: 5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3 -percent slope), each standpipe shall be provided with a two-way hose connection located either... (remainder of paragreph unchanged) ... (Reason: Reduced the amount of pressure required to facilitate testing, and provides backup protection for fire fighter safety.) "Section 905.9, add a second paragraph after the exceptions to read as follows: (Reason: To avoid significant water losses. Consistent with amendment to IFC 903.4.) "Add Section 907.1.3 to read as follows: North Central Texas 11 September 2007 2006 IFC Amendments months of permit application. (Reason: Consistent with local practice.) —Section 907.2.1; change to read as follows: 907.2.1 Group A. A manual fire alar system shall be installed in Group A occupancies having an occupant load of 300 or more Persons or more than 100 Persons above or below the lowest level of exit discharge. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alar system as required for the Group E occupancy. (Reason. Increases the requirement is changed to be consistent with Group 8 requirenrent.) "Section 907.2.3; change to read as follows: 907.2.3 Group E. A manual fire alar system shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alar system. An approved smokedetection system shall be installed in (Reason: To distinguish educational from day care occupancy minimum protection requirements. Further, to define threshold at which portable buildings are considered a separate building for the purposes of alarm systems.) -"Section 907.2.3; change exception #f and add exception #1.1 to read as follows: occupancies with an occupant load of less than 50 when (Reason: Consistent with Texas State laws concerning day care facility requirements.) Option A '*Section 907.2.12; change to read as follows: 907.2.12 High-rise buildings. Buildings with any floor used for human occupancy located more than 75 feet (22 860 mm) above the lowest level (balance unchanged) North Central Texas 12 September 2007 2006 IFC Amendments "Section 907.2.12; change to read as follows: 907.2.12 High-rise buildings. Buildings with any floor used for human occupancy located more than 75 55 feet (22 860 764 mm) above the lowest level of Ore department vehicle access shall be provided with an automatic fire alarm system and an emergency voicetalann communications system in accordance with Section 907.2.12.2. (Reason: To correct definifr'on of high-rise for Option B jurisdictions.) "Section 907.2.12, exception #3, change to read as follows: 3. Buildings with an occupancy in Group A-5 in accordance with Section 303.1 of the International Building Code, when used for open air seeing: however, this exception does not apply to accessory uses including but not limited to sky boxes restaurants and similarly enclosed areas. (Reason: To indicate that enclosed areas within open air seating type occupancies are not excepted from automatic fire alamn system requirements) "Section 907.4; add a second paragraph to read as follows: Manual alarm actuating devices shall be an approved double action type. (Reason: Consistent with local requirements.) —Add Section 907.6.1 to read as follows 907.6.1 Installation. All fire alarm systems shall be installed in such a manner that a failure of anv single initiating device or single open in an initiating circuit conductor will not interfere with the normal operation of other such devices. All initiating circuit conductors shall be Class "A" wired with a minimum of six feet separation between supply and return circuit conductors IDC – Class "A" Style D� SLC - Class "A" Style 6: NAC - Class "B" Style Y. The IDC from an addressable device used to monitor the status of a suppression system may be wired Class B Style B provided the distance from the addressable device is within 10 -feet of the suppression system device. (Reason: To provide uniformity in system specifications and guidance to design engineers) Option A "Section 907.9.2, change to read as follows: 907.9.2 407 6.2 High-rise buildings. In buildings with a any floor used for human occupancy that is located more than 75 feet (22 860 mm) above the lowest level ... {remainder of section unchanged). North Central Texas 13 September 2007 2006 IFC Amendments Option B **Section 907.9.2; change to read as follows: 907.9.2 High-rise buildings. In buildings that have a any floor used for human occupancy that is located more than 75 55 feet (22.660 16 764 mm) above the lowest level ... (remainder of section unchanged). (Reason: Correct definition of high-rise for Option B jurisdictions) *' Section 910. t; Amend exception 2 to reed as follows: 4. Where areas of buildings are equipped with early suppression fast -response (ESFR) sprinklers, 2utemafisoniv manual smoke and heat vents shall nePbe required within these areas. (Reason: Allows the fire department to control the smoke and heat during and after a fire event.) "'Section 910.2; Add subsection 910.2.4 and exceptions to read as follows: Exceptions: (Reason: Maintain the current level of protection as outlined in the 2003 IFC.) North Central Texas 14 September 2007 2006 IFC Amendments —Table 910.3; Change the ride of the first row of the table from "Group F! and S-1" to include "Group H" and to read as follows: Group N F-1 and $-1 (Reason: Consistency with the amendment 910.2.4 to include Group H) "'Section 910.3.2.2; Add second paragraph to read as follows: The automatic operating mechanism of the smoke and heat vents shall operate at a temperature rating at least 100 degrees (F) (approximately 38 decrees Celsius) greater than the temperature rating of the sprinklers installed. (Reason: Specifies a temperature range at which smoke and heat vents should activate in sprinklered buildings to ensure that the sprinkler system has an opportunity to activate and control the Ore prior to vent operation.) "`Section 913.1–Add second paragraph and exception to read as follows: (Reason: This requirement allows fire fighters safer access to the fire pump room. The requirement allows access without being required to enter the building and locate the fire pump room interior access door during a fire event. The exception recognizes that this will not always be a feasible design scenario for some buildings, and as such, provides an acceptable alternative to protect the pathway to the fire pump room) - —Section 1017.1; add an exception #5 to read as follows: connected to the building's fire alarms stem where such a system is provided. (Reason: Consistent with regional amendment to IBC 1017. 1.) North Central Texas 15 September 2007 2006 IFC Amendments Option A **Section 1020.1.7; change to read as follows: 1020.1.7 Smokeproof enclosures. In buildings required to comply with Section 403 or 405 of the IBC, each of the exits of a building that serves stories where the any floor surface is located more than 75 feet (22 860 mm) above the lowest level of fire ... fremainder of section unchanged) Option B **Secdon 1020.1.7; change to read as foltows: 1020.1.7 Smokeproof enclosures. In buildings required to comply with Section 403 or 405 of the IBC, each of the exits of a building that serves stories where the a� floor surface is located more than 75 55 feet (22660 16 764 mm) above the lowest level of fire ... {remainder of section unchanged). (Reason: Correct definition of high-rise for Option Sjurisdictions.) ***Section 1028.2, change to read as follows: 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exile are . Security devices affecting means of egress shall be subject to approval of the fire code official. (Reason: Maintain a current level of protection as identified in the 2003 and provide firefighter safety.) "Section 1504.4; change to read as follows: 1504.4 Fire Protection. New and existing spray Spray booths and spray rooms shall be protected by an approved automatic fire -extinguishing system ... [remainder of section unchanged)... (Reason: Consistent protection in all spray booths.) ***Section 2204.1; change to read as follows: 2204.1 Supervision of dispensing. The dispensing of fuel at motor fuel -dispensing facilities shall be Gerdui;ted­by� qualified attendant or shall be under in 9 supervision of a qualified attendant at all thin sha&be in accordance with Section -2204. [he following: 1. Conducted by a qualified attendant and/or, 2. Shall be under the supervision of a qualified attendant and/or 3. Shall be an unattended self-service facility in accordance with Section 2204.3. At any. time the. qualified attendant of item #1 or #2 above is not Present, such operations shall be North Central Texas 16 September 2007 2006 IFC Amendments considered as an Unattended self-service facility and shall also comply with Section 2204.3. (Reason: Allows a facility to apply the attended and unattended requirements of the code when both are met) (Reason: To provide protection for worst-case scenario in flexible or unknown situations.) '"'Table 2306.2; replace text of "footnotei" to read as follows: i. Where areas of buildings are equipped with early suppression fast -response (ESFR) sprinklers only manual smoke and heat vents shall be required within these areas. (Reason: Allows the fire department to control the smoke and heat during and after a fire event.) **Section 3301.1.3; change to read as follows: 3301.1.3 Fireworks. The possession, manufacture, storage, sale, handling and use of fireworks are prohibited. Exceptions: 1. Only when approved for fireworks displays storage and handling of fireworks as allowed in Section 3304 and 3308. 2. Manufactum, assembly and testing ofilrewoft as allowed in Section 3204 3—The use of fireworks for approved display as allowed in Section 3308. 4. The PGSGR--: OR 60-61 MOF fifa'V-648 (Reason: Restricts to approved displays, which is consistent with local practice.) North Central Texas 17 September 2007 2006 IFC Amendments Option A -*Section 2302; add a second paragraph to the definition of "High -Piled Combustible Storage" to read as follows., read as follows: Any building exceeding 12,000 s .ft. that has a clear height in excess of 12 feet makin it possible to be used for storage in excess of 12 feet shall be considered to be hi h fled storage and shall comply with the provisions of this section. When a specific product cannot be identified a fire protection system shall be installed as for Class IV commodities to the maximum pile height height. (Reason: To provide protection for worst-case scenario in flexible or unknown situations.) '"'Table 2306.2; replace text of "footnotei" to read as follows: i. Where areas of buildings are equipped with early suppression fast -response (ESFR) sprinklers only manual smoke and heat vents shall be required within these areas. (Reason: Allows the fire department to control the smoke and heat during and after a fire event.) **Section 3301.1.3; change to read as follows: 3301.1.3 Fireworks. The possession, manufacture, storage, sale, handling and use of fireworks are prohibited. Exceptions: 1. Only when approved for fireworks displays storage and handling of fireworks as allowed in Section 3304 and 3308. 2. Manufactum, assembly and testing ofilrewoft as allowed in Section 3204 3—The use of fireworks for approved display as allowed in Section 3308. 4. The PGSGR--: OR 60-61 MOF fifa'V-648 (Reason: Restricts to approved displays, which is consistent with local practice.) North Central Texas 17 September 2007 2006 IFC Amendments Option B ' Sectfon 2302; add a second paragraph to the definition of "High -Piled Combustible Storage" to read as follows: Any building exceeding 6,000 sa.ft that has a clear height in excess of 12 feet making it possible to be used for storage in excess of 12 feet shall be considered to be high -oiled storage and shall comply with the provisions of this section. When a specific product cannot be identified a fire Protection system shall be installed as for Class IV commodities to the maximum pile height. (Reason: To provide protection for worst-case scenario in flexible or unknown situations.) '"'Table 2306.2; replace text of "footnotei" to read as follows: i. Where areas of buildings are equipped with early suppression fast -response (ESFR) sprinklers only manual smoke and heat vents shall be required within these areas. (Reason: Allows the fire department to control the smoke and heat during and after a fire event.) **Section 3301.1.3; change to read as follows: 3301.1.3 Fireworks. The possession, manufacture, storage, sale, handling and use of fireworks are prohibited. Exceptions: 1. Only when approved for fireworks displays storage and handling of fireworks as allowed in Section 3304 and 3308. 2. Manufactum, assembly and testing ofilrewoft as allowed in Section 3204 3—The use of fireworks for approved display as allowed in Section 3308. 4. The PGSGR--: OR 60-61 MOF fifa'V-648 (Reason: Restricts to approved displays, which is consistent with local practice.) North Central Texas 17 September 2007 2006 IFC Amendments -Section 3302; change the definition of "Areworks" to read as follows: FIREWORKS. Any composition or device for the purpose of producing a visible or an audible effect for entertainment purposes by combustion, deflagration, or detonation and/or activated by ignition with a match or other heat Producing device that meets the definition of 1.4G fireworks or 1.3G fireworks as set forth herein. (Reason: Increased safety from fireworks related injuries.) —Section 3403.6; add a sentence to read as follows: An approved method of secondary containment shall be provided for underfround tank and piping systems. "Section 3404.2.11.5; add a sentence to read as follows: An approved method of secondary containment shall be provided for underground tank and pipina systems. (Reason: Increased protection in response to underground leak problems and remediation difficulty, in underground applications.) —Section 3404.2.11.5.2; change to read as follows 3404.2.11.5.2 Leak detection. Underground storage tank systems ... (bulk of provision unchanged) ... and installed in accordance with NFPA 30 and as specified in Section 3404.2.11.5.3. (Reason: Reference to Section 3404.2.11.5.3 amendment) • Add Section 3404.Z 11.5.3 to read as follows: the dispensers, a minimum of two are required. (Reason: Provides an economical means of checking potential leaks at each tank site.) -Delete Section 3406.5.4.5 and replace with the following: 3406.5.4.5.1 Site requirements. 1. Dispensing may occur at sites that have been permitted to conduct mobile fueling. North Central Texas 18 September 2007 2006 IFC Amendments 9 3, 4, 5, 3406.5.4.5.2 Refuelina Operator Re uir ents i. The owner of a mobile fuelma operations shall 2. 3. 4. 5. 6. 7. 8. 9. 10. emergency. 3406.5.4.5.3 Operational Requirements. 1. The tank vehicle disoensina eoutomen Q 3. 4. 5, North Central Texas 19 September 2007 2006 IFC Amendments 0 7. 8. (Reason: Provides clarity and organization of the site, operation and use requirements.) -Add Section 3803.2.1.8 to read as follows: containers by a distance f not less than 20 feet. (Reason: To provide a consistent and reasonable means of regulating the use of portable LP -Gas containers in these situations.) "Section 3804.2; add an exception #2 to read as follows: Exceptiong: 1. (existing exception unchanged) 2. Except as permitted in 308.3 and 3804.3.2 LP- as containers are not Permitted in residential areas. (Reason: To provide a consistent and reasonable means of regulating the use of portable LP -Gas containers. References regional amendment to IFC 3804.3.2.) Add Section 3804.3.2 to read as follows: 3804.3.2 Spas, Pool Heaters and other listed devices. Where natural eas service is not available. LP - Gas containers are allowed to be used to supply spa and pool heaters or other listed devices Such containers shall not exceed 250 -Gallon water capacity. See Table 3804.3 for location of containers (Reason: Allows for an alternate fuel source.) rgAry North Central Texas 20 September 2007 2006 IFC Amendments The provisions contained in this appendir are not mandatory unless specifically referenced in the adopting ordinance. SECTION 8101 GENERAL B101.1 Scope. The procedure for determining foe -flow re- quirements for buildings or portions of buildings hereafter con- structed shall be in accordance with this appendix. This appendix does not apply to structures other than buildings. SECTION 8102 DEFINITIONS B102.1 Definitions. For the purpose of this appendix, certain terms me defined as follows: - FIRE FLOW. The flow rate of a water supply, measured at 20 pounds per square inch (psi) (138 kPa) residual pressure, that is available for the fighting. 1 FIRE -FLOW CALCULATION AREA. The floor area, in aquae feet (m'), used to determine the required fire flow. SECTION 8103 MODIFICATIONS 8103.1 Decreases. The fire chief is authorized to reduce the fire -flow, requirements for isolated buildings or a group of buildings in rural areas or small communities where the devel- opment of full fire -flow requirements is impractical. B103.2 Increases. The foe chief is authorized to increase the fire -flow requirements where conditions indicate an unusual susceptibility to group fires or conflagrations. An increase shall not be more than twice that required for the building under con- sideration. B103.3 Areas without water supply systems. For informa- tion regarding water supplies for fire -fighting purposes in rural and suburban areas in win ch adequate and reliable water supply systems do not exist, the fire code official is authorized to uti- lize NFPA 1142 or the International Urban Wildland Interface Code. SECTION B104 FIRE AREA B104.1 General. The fire -flow calculation area shall be the to- tal fear area of all four levels within the exterior walls, and un- der the horizontal projections of the roof of a building, except as modified in Section B 104.3. 13104.2Areaseparation. Portions of buildings which are sepa- rated by firewalls without openings, constructed in accordance with the International Building Code, are allowed to be consul- erect as separate fire -flow calculation areas. B104.3 Type IA and Type lB construction. The fire -flow cal- 1 culation area of buildings constructed of Type IA and Type IB construction shall be the area of the three largest successive floors. Exception: Fire -flow calculation area for open parking ga- 1 rages shall be determined by the area of the largest floor. SECTION 8105 FIRE -FLOW REQUIREMENTS FOR BUILDINGS BI05.1 One- and two-family dwellings. The minimum fire -flow requirements for one- and two-family dwellings hav- ing a fire -flow calculation area which does not exceed 3,600 1 square feet (344.5 ms) shall be 1,000 gallons per minute (3785.4 Umin). Fire flow and flow duration for dwellings hav- ing a fire -flow, calculation area in excess of 3,600 square feet 1 (344.5 m°) shall not be less than that specified in Table B 105.1. Exception: A reduction in required fire flow of 50 percent, as approved, is allowed when the building is provided with an approved automatic spriniler system. B105.2 Buildings other than one -and two-family dwellings. The minimum fire flow and flow duration for buildings other than one, and two-family dwellings shall be as specified in Ta- ble B105.1. Exception: A reduction in required fire flow of up to 50 percent, as approved, is allowed when the building is pin- vided with an approved automatic spriniler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 of the In- ternationalrine Code. Where buildings are also of Type Ior B constriction and are a light -hazard occupancy as defined by NFPA 13, the reduction may be up to 75 percent. The re- sulting fire flow shall not be less than 1,500 gallons per min- ute inute (5678 I/min) for the prescribed duration as specified in Table B 105.1. SECTION 8106 REFERENCED STANDARDS ICC IBC International Building Code 81042, Table B 105.1 ICC IFC International Fire Code B105.2 ICC RIWIC International Urban - 81093 Wildland Interface Code Standard on Water Supplies NFPA 1142 for Suburban and Rural Fire B 103.3 Fighting 2003 INTERNATIONAL FIRE CODED 371 FIRE -FLOW REQUIREMENTS FOR BUILDINGS TABLE 8105.1 MII.IIMIIN PFMIIG FO FIFiF FI . ANO FI AW riI IR GTICIN F . PINI OINRSa FIRE -FLOW CALCULATION ARE oars HM FIRE FLOW galloon per minute)` FLOW DURATION ((worn) IA antl IS' Type IIA antl IIIA' Typ, IV and V-A° IIB antl 1118° V-0° 022,700 0-12,7W 0-8,200 0-5,900 0-3,600 1,500 22,701-30,200 12,701-17,OW 8,201-10,900 5,901-7,900 3,601-4,800 1,750 30201-38,700 17,001-21,800 10,901-12,900 7,901-9,800 4,801-6,200 2,000 38,701-48,300 21,801-24,200 12,901-17,40O 9,801-12,600 6,201-7,700 2,250 2 48,301-59,000 24,201-33,200 17,401-21,300 12,601-15,400 7,701-9,400 2,500 59,WI-70,900 33,201-39,700 21,301-25,500 15,401-18,400 9,401-11,300 2,750 70,901-83,700 39-701-47,100 25,501-30,100 18,401-21,800 11,301-13,400 3,000 83,701-97,700 47,107-54,900 30,101-35,200 21,801-25,900 13,401-15,600 3,250 97,701-112,700 54,907-63,400 35,20140,600 25,901-29,300 75,601-IR,OW 3,500 112,701-128,700 63,401-72,400 40,601-46,400 29301-33,500 18,001-20,600 3,750 128,701-145,900 72,401-82,100 46,401-52,500 33,501-37,900 20,601-23,300 4000 145,901-164,200 82,101-92,400 52,501-59,100 37,901-42,700 23,301-26,300 4,250 164,201-183,400 92,401-103JO0 59,101-66,000 42,701-47,700 26,301-29,300 4,500 183,401-203,700 103,101-114,600 66,001-73,300 47,701-53,000 29,301-32,600 4,750 203,701-225,200 114,601-126,700 73,301-81,100 53,001-58,600 32,601-36,000 5,000 225,201-247,700 126,701-139,400 81,101-89,200 5001-65,400 36,001-39,6(M 5,250 247,701-271,200 139,401452,600 89,201-97,700 65,401-70,600 39,601-43,400 5,500 271,201-295,900 152,601-166,500 97,701-106,500 70,601-77,000 43.401-47,400 5,750 295,901-Gmater 166,501 -Greater 106,501-115,800 77,001-83,700 47,401-51,500 6,000 4 115,801-125,500 83,701-90,600 51,501-55,700 6,250 125,501-135,500 90,601-97,900 55,701-60,200 6,500 135,501-145,800 97,901-106,800 60,201-64,800 6,750 145,801-156,700 106,801-113,200 64,801-69,600 7,000 156,701-167,900 113,201-121,300 69,601-74,600 7,250 167,901-179,4(%) 121,301-129,600 74,601-79,800 7,500 11-191,400 129,601-138,300 79 801-85,100 7,750 1M1 -created' 138,301 -Greater 85,101 -Great, 8,0W Por SL Isquarefom=011929m�.lgallonparminuw=3.785Um,lpoundper>uareireh=6B95kPa a. The minimum required fire flow shall be permitted m bn reduced by 25 proem for Use Group K b. Types of wn vuction are based on the fnreraarionai B.ddu q Cbde. , M.,tee at20poi. 372 2003 APPENDIX C FIRE HYDRANT LOCATIONS AND DISTRIBUTION The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. SECTION C101 GENERAL C101.1 Scnpe. Fire hydrants shall be provided in accordance with this appendix for the protection of buildings, orponions of buildings, hereafter constructed. SECTION C102 LOCATION C102.1 Fire hydrant locations. Fire hydrants shall be pro- vided along required fire apparatus access roads and adjacent public streets. SECTION C103 NUMBER OF FIRE HYDRANTS C103.1 Fimbydr tsavailable.'Fhemininmmnumberoffive hydrants available to abuilding shall not be less than that listed in 'Fable 0105.1. The number of fire hydrants available to a complex or subdivision shall not be less than that determined by spacingrequirements listedin TableC105.1 when applied to fire apparatus access roads and perimeter public streets from which fire operations could be conducted. SECTION C104 CONSIDERATION OF EXISTING FIRE HYDRANTS C104.1 Existing fire hydrants. Existing fire hydrants on pub- lic streets are allowed to be considered as available. Existing fire hydrants on adjacent properties shall not be considered available unless fire apparatus access roads extend between properties and easements are established to prevent obstruction of such roads. SECTION C105 DISTRIBUTION OF FIRE HYDRANTS C105.1 Hydrant spacing. The average spacing between fire hydrants shall not exceed that listed in Table C105.1. Exception: The fire chief is authorized to accept a defi- ciency of up to 10 percent where existing fire hydrants pro- vide a0 or a portion of the required fire hydrant service. Regardless of the average spacing, fire hydrants shall be lo- cated such that all points on sneers and aecessroads adjacent to a building are within the distances fisted in Table C105.1. TABLE CtOS.t NUMBER AND DISTRIBUTION OF FIRE HYDRANTS RRE FLOIN REQUIREMENT (inson MINIMUM NUMBER OF HYDRANTS AVERAGE SPACING BETWEEN HYDRANTS"' (feet) MAXIMUM DISTANCE FROM ANY POINT ON STREET OR ROAD FRONTAGE TO A HYDRANT° 1,750 or less 1 500 250 2,0()12,250 2 _450 225 _ 2,500 _- 3 450 _.._ 225 3,000 3 400 225 3,500-4,01h 4 350 4,500-5,000 5 300 180 5,500 -.......—... 6 300 180 6,000 6 250 150 6,500-7,000 7 250 150 7,500 or mora _ 8 or more 200 120 For SL ifoot=3M.8 mm,lgatlon per minute=3.785 Vm. a. Reduce by 100 feet for dead-end snouts or roads. h. wherestreetsareprovidedwimmediandividerswhichembecrossedbyfirefighterse sh4lavemge5 orwherearterialsbeetsareprovidedwimgedonmore tometin bens up afire -ams ntofmamptof 3,0(0 vapors per mature and feet for aliavarmgn5owmopnenterimeofineencetaWbearzavgedonwal- ternadng basis up m s flr�flew reguimment of 9,000 gallons per minuto and 400 feat for higher &e-Oow requiremenrs. a Where tsps mer mato eso e l LOGO R d topmets wherabydrants aro hummdded forprolaction of swcNrea or similar fire problems, fire hydrants shaltbe pm vided at spacing or to exceed 1,100 fcct to provide for traosponxtion hazards. d. Reduce by 50 feet for deadnotstreets or roads. e. One bydrent for each 1,000 gallons per minute or fracnon mercof. 2003 INTERNATIONAL FIRE CODE® 373 APPENDIX D FIRE APPARATUS ACCESS ROADS Theprovisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance SECTION D101 D103.3 Turning radius. The minimum turning radius shall be GENERAL determined by the fire code official. D1011 Scope. Fire apparatus access roads shall be in accor- D303.4 Dead ends. Dead-end fire apparatus access roads in dance with this appendix and all other applicable requirements excess of 150 feet (45 720 mm) shall be provided with width of the International Fire Code. and turnaround provisions in accordance with Table D103.4. SECTION D102 REQUIRED ACCESS D102.1 Accessand loading. Facilities, buildings orportions of buildings hereafter constructed shall be accessible to fire de- parwient apparatus by way of an approved fire apparatus access road with an asphalt, concrete or other approved driving sur- face capable of supporting the imposed load of fire apparatus weighing at least 75,000 pounds (34 050 Seg). SECTION 0103 MINIMUM SPECIFICATIONS D103.1 Access road width with a hydrant. where a fire by - dram is located on a fire apparatus access road, the minimum road width shall be 26 feet (7925 mm). See Figure D103.1. D103.2 Grade. Fire apparatus access mads shall not exceed 10 percent in grade. F,xception: Grades steeper than 10 percent as approved by the frre chief. TABLE D103.4 REQUIREMENTS FOR DEAD-END FIRE LENGTH WIDTH (feat) (teal) TURNAROUNDS REQUIRED 0-150 20 None required _ 120 -foot Hammerhead, 60400t "Y" or 151-500 20 96 -foot -diameter cul-de-sac in accordance with Figure D103.1 120 -foot Hammerhead, 60400t "Y" or 501-750 26 96 -foot -diameter cul -de -sae in accordance with Fig. D103.1 Over 750 Special approval requimd For Si: 1 fax -304.8 nun. D103.5 Fire apparatus access road gates. Gates securing the fire apparatus access roads shall comply with all of the follow- ing criteria: 1. The minimum gate width shall be 20 feet (6096 mm). 0y —gg70'.... ._ / (�/212dR 26' 28'R VR. 28' R -20' TVP.' 2W TYP.' 26' 20' 9W DIAMETER 70'DIAMETER ACCEPTABLE ALTERNATIVE MINIMUM CLEARANCE CUL-DE-SAC CUL-DE-SAC TO 120' HAMMERHEAD AROUND A FIRE HvDRANT 30'20' 60'1d �TM 28'.R— 28'R ...-TO'-.. TYP P20' ­T20' TV26' 20' 20' 60' HAMMERHEAD. 12W HAMMERHEAD ACCEPTABLE ALTERNATIVE TO 120' HAMMERHEAD Fm SL 1foW=30418 tan. FIGURED103.1 DEAD-END FIRE APPARATUS ACCESS ROAD TURNAROUND 2003 INTERNATIONAL FIRE CODE® 375 APPENDIX D 2. Gates shall be of the swinging or sliding type. 3. Construction of gates shall be of materials that allow manual operation by one person. 4. Gate components shall be maintained in an operative condition at all times and replaced or repaired when de- fective. 5- Electric gates shall be equipped with a means of opening the gate by fire department personnel for emergency ac- cess, Emergency opening devices shall be approved by the fire code official. 6. Manual opening gates shall not be looked with apadlock or chain and padlock unless they are capable of being opened by means of forcible entry tools. 7. Locking device specifications shall be submitted for ap- proval by the fire code official. D103.6 Signs. Where required by the fire code official, fire ap- paratus access roads shall be marked with permanent NO PARKING—FIRE LANE signs complying with Figure D 103.6. Signs shall have a minimum dimension of 12 inches (305 mm) wide by 18 inches (457 mm) high and have red letters on a white reflective background. Signs shall be posted on one or both sides of the fire apparatus road as required by Section D103.6.1 of D103.6.2. SIGN TYPE "A" SIGN TYPE 'C' SIGN TYPED" I'D NO _......,,No.......,- PARKING PARKING PARKING 6^ FIRE LANE FIRE LANE FIRE LANE �.. 12._..� _.... 12'-- -12'--' FIGURE Waste FIRE LANE SIGNS D103.6.1 Roads 20 to 26 feet in width. Fire apparatus ac- cess roads 20 to 26 feet wide (6096 to 7925 mm) shall be posted on both sides as a fire lane. D103.6.2 Roads more than 26 feet in width. Fire appara- tus access roads more than 26 feet wide (7925 mm) to 32 feet wide (9754 mm) shall be posted on one side of the road as a fire lane. SECTION D104 D104.1 Buildings exceeding three stories or 30 feet in height. Buildings or facilities exceeding 30 feet (9144 mm) or three stories in height shall have at least three means of fire ap- paratus access for each structure. D104.2 Buildings exceeding 62,010 square feet in area. Buildings or facilities having a gross building amaof more than 62,000 square feet (5760 tor) shall be provided with two sepa- rate and approved fire apparatus access roads. Exception: Projects having a gross building area of up to 124,000 square feet (11520 m2) that have a single approved fire apparatus access road when all buildings are equipped throughout with approved automatic sprinkler systems. D104.3 Remoteness. Where two access roads are required, they shall be placed a distance apart equal to not less than one half of the length of the maximum overall diagonal dimension of the property or area to be served, measured in a straight line between accesses.f� G S4 F� r j::Vjc k t /o.' SECTION D105 AERIAL FIRE APPARATUS ACCESS ROADS D105.1 Where required. Buildings or portions of buildings or facilities exceeding 30 feet (9144 mm) in height above the low- est level of fire department vehicle access shall be provided with approved fire apparams access roads capable of accom- modating fire department aerial apparatus. Overhead utility and power lines shall not be located within the aerial fire appa- ratus access roadway. D105.2 Width. Fire apparatus access roads shall have a mini- mum unobstructed width of 26 feet (7925 mm) in the immedi- ate vicinity of any building or portion of building more than 30 feet (9144 mm) in height. D105.3 Proximity to building. At least one of the required ac- cess routes meeting this condition shall be located within a minimum of 15 feet (4572 mm) and a maximum of 30 feet (9144 mm) from the building, and shall be positioned parallel to one entire side of the building. SECTION D106 M TS D106.1 Projects having more than 100 dwelling units. Mul- tiple -family residential projects having more than 100dwelling units shall be equipped throughout with two separate and ap- proved fire apparatus access roads. Exception: Projects having up to 200 dwelling units may have a single approved fire apparatus access road when all buildings, including nonresidential cuoupancies, are equipped throughout with approved automatic sprinkler systems installed in accordance with Section 903.3.1.1 or 903.3.1.2 of the International Fire Code. D106.2 Projects having more than 200 dwelling units. Mul- tiple -family residential projects having more than 200 dwelling units shall be provided with two separate and approved fire ap- paratus access roads regardless of whether they are equipped with an approved automatic sprinkler system. ONE- OR TWO-FAMILY RESIDENTIAL DEVELOPMENTS P- 376 20M INTERNATIONAL FIRE CODES APPENDIX D 1. 104 t'e there are 30 or fewer dwelling units on a single pM4c or private access way and all dwelling units are p&Wcted by approved residential sprinkler systems, mss from two directions shall not be required. 2. Tumber of dwelling units on a single fire appara- tMecess road shall not be increased unless fire appa- rfrus access roads will connect with future d0ftpment, as determined by the fire code official. 2003 INTERNATIONAL FIRE CODE® 377 APPENDIX E HAZARD CATEGORIES The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. SECTION E10i GENERAL E101.1 Scope. This appendix provides information, explana- tions and examples to illustrate and clarify the hazard catego- ries contained in Chapter 27 of the International Fire Code. The hazard categories arebased upon the DOL 29 CFR. Where numerical classifications ave included, they are in accordance with nationally recognized standards. This appendix should not be used as the sole means of haz- ardous materials classification. SECTION E102 HAZARD CATEGORIES E102.1 Physical hazards. Materials classified in this section pose a physical hazard. E102.1.1 Explosives and blasting agents. The current UN/DOT classification system recognized by international authorities, the Department of Defense and others classifies all explosives as Class 1 materials. They are then divided into six separate divisions to indicate their relative hazard. There is not a direct correlation between the designations used by the old DOT system and those used by the current system nor is them correlation with the system (high and low) established by the Bureau of Alcohol, Tobacco and Firearms (BATF). Table 3304.3 provides some guidance with regard to the current categories and their relationship to the oldcatmories. Some items may appearin more than one division, dependingon factors such "a degreeofconfine- ment or separation, by type of packaging, storage configum- tion or state of assembly. In order to determine the level of hazard presented by ex- plosive materials, testing to establish quantitatively their ex- plosive nature is required. There are numerous test methods that have been used in establish the character of an explosive material. Standardized tests, required for finished goods containing explosives or explosive materials in a packaged form suitablefor shipmentor storage, have been established by UN/DOT and BATF. However, these tests do notconsider key elements that should be examined in a manufacturing situation. In manufacturing operations, the condition and/or the state of a material may vary within the process. The in -process material classification and classification require- ments for materials used in the manufacturing process may he different from the classification of the same material when found in finished goods depending on the stage of the process in which the material is found. A classification methodology must beused that recognizes the hazards com- mensurate with the application to the variable physical con- ditions as well as potential variations of physical character and type of explosive under consideration. Test methods or guidelines for hazard classification of ener- getic materials used for in -process operations shall be ap- proved by the fire code official. Test methods used shall be DOD, BATF, UNIDOT or other approved criteria. The re- sults of such testing shall become a portion of the files of the jurisdiction and be included as an independent section of any Hazardous Materials Management Plan (HMMP) re- quired by Section 3305.2.1. Also see Section 104.6.2. Examples of materials in various Divisions are as fol- lows: 1. Division 1.1 (High Explosives). Consists of explo- sives that have a mass explosion hazard. A mass ex- plosion is one which affects almost the entire pile of material instantaneously. Includes substances that, when tested in accordance with approved methods, can be caused to detonate by means of a blasting cap when unconfined or will transition from deflagration to a detonation when confined or unconfined. Exam - pies: dynamite, TNT, nitroglycerine, G3, HMX, RDX, encased explosives, military ammunition. 2. Division 1.2 (Low Explosives). Consists of explo- sives that have a projection hazard, but not a mass ex- plosion hazard. Examples: nondetonating encased explosives, military ammunition and the like. 3. Division 1.3 (Low Explosives). Consists of explo- sives that have a fire buzzard and either a minor blast hazard or a minor projection hazard or both, but not a mass explosion hazard. The major hazard is radiant heat or violent burning, or both. Can be deflagrated when confined. Examples: smokeless powder, pro- pellant explosives, display fireworks. 4. Division 1.4. Consists of explosives that pose a minor explosion burned, The explosive effects are largely confined to the package and no projection of frag- ments of appreciable size or range is expected. An in- ternal fire must not cause virtually instantaneous explosion of almost the entire contents of the pack- age. Examples: squibs (nondetonating igniters), ex- plosive actuators, explosive trains (low level detonating cord), 5. Division 1.5 (Blasting Agents). Consists of very in- sensitive explosives. This division is comprised of substances which have a mass explosion hazard, but are so insensitive that there is very little probability of initiation or of transition from burning to detonation under normal conditions of transport. Materials am not cap sensitive; however, they are mass detonating when provided with sufficient input Examples: oxidizer and liquid Nei slurry, and gels, am- monium nitrate combined with fuel oil. 20031NTERNATIONAL FIRE CODE® 379 u"40,104 6. Division 1.6- Consists of extremely insensitive arti- cles which do not have a mass explosive hazard. This division is comprised of articles which contain only extremely insensitive detonating substances and which demonstrate a negligible probability of acei dental initiation or propagation. Although this cate- gory of materials has been defined, the primary application is currently limited to military uses. Ex comes: Low vulnerability military weapons. Explosives in each division are assigned compatibility group letter by the Associate Administrator for Hazardous Materials Safety (DOT) based on criteria specified by DOTn 49CFR. Compatibility group letters are used to spec- ify the controls for the transportation and storage related to various materials to prevent an increase in hazard that might result if certain types of explosives were stored or trans- ported together. Altogether, there are 35 possible classifica- tion codes for explosives, e.g-, 1.1 A, 1.3C, 1.4S, etc. E102.1.2 Compressed gases. Examples include: 1. Flammable: acetylene, carbon monoxide, ethane, eth- ylene, hydrogen, methane. Ammonia will ignite and burn although its flammable range is too narrow for it to fit the definition of flammable gas. 2. Oxidizing: oxygen, ozone, oxides of nitrogen, chlo- rine and fluorine. Chlorine and fluorine do not contain oxygen but reaction with flammables is similar to that of oxygen. 3. Corrosive: ammonia, hydrogen chloride, fluorine. 4. Highly toxic: arsine, cyanogen, fluorine, germane, hydrogen cyanide, nitric oxide, phosphine, hydrogen selenide, stibine. 5. Toxic: chlorine, hydrogen fluoride, hydrogen sulfide, phosgene, silicon tetratluoride. 6. Inert (chemically unreactive): argon, helium, kryp- ton, neon, nitrogen, xenon. 7. Isymphoric: diborane, dichloroborane, phosphine, silane. 8. Unstable (reactive): butadiene (unstabilized), ethyl- ene oxide, vinyl chloride. E102.1.3 Flammable and combustible liquids. Examples include: 1. Flammable liquids. Class IA liquids shall include those having flash points below 73'F CYQ and having a boiling point at or below 100°F (38°C. Class 114 liquids shall include these having flash points below 73°F (23°C) and having a boiling point at or above 100°F (38'C). Class IC liquids shall include those having flash points at or above 73"F (23'C.) and below 100'T (38'C). 2. Combustible liquids. Class 11 liquids shall include those having flash points at or above 100°F (38°C) and below 140°F (60°C). Class IIIA liquids shall include those having flash points at or above 140°F (60`C) and below 200°F (93°C). Class IIIB liquids shall include those liquids hav- ing flash points at or above 200°F (9YC). E102.1.4 Flammable solids. Examples include: I. Organic solids: camphor, cellulose nitrate, naphtha- lene. 2. Inorganic solids: decaborane, lithium amide, phos- phorous heptasubble, phosphorous sesquisulfide, po- tassium sulfide, anhydrous sodium sulfide, sulfur. 3. Combustible metals (except dusts and powders): ce- sium, magnesium, zirconium. E102.1.5 Combustible dusts and powders. Finely divided flammable solids which may be dispersed in air as a dust cloud: wood sawdust, plastics, coal, flour, powdered metals (few exceptions). E102.1.6 Combustible fibers. See Section 2902.1. / E102.1.7 Oxidizers. Examples include: 1- Gases: oxygen, ozone, oxides of nitrogen, fluorine and chlorine (reaction with flammables is similar to that of oxygen). 2. Liquids: bromine, hydrogen peroxide, nitric acid, perchloric acid sulfuric acid. 3. Solids: chlorides, chromates, chromic acid, iodine, ni- trates, nitrites, perchlorates, peroxides. E102.1.7.1 Examples of liquid and solid oxidizers ac- cording to hazard. Class 4: ammonium perchlorate (panicle size greater than 15 microns), ammonium permanganate, guanidine nitrate, hydrogen peroxide solutions more than 91 percent by weight, perchloric acid solutions more than 72.5 percent by weight, potassium superoxide, teuanitromethane. Class 3: ammonium dichromate, calcium hypochlorite(over 50 percent by weight), ehloric acid (10 percent maximum concentration), hydrogen peroxide solutions (greater than 52 percent up to 91 percent), mono-(trichloro)-tetra-(monopotassium dichloro)-penta-s-triaxinetrione, nitric acid, (fuming —more than 86 percent concentration), perchloric acid solutions (60 percent to 72 percent by weight), potassium bromate, potassium chlorate, potassium dichloro-s-triazinetrione (potassium dichloro- isocyanurate), sodium bromate, sodium chlorate, so- dium chlorite (over 40 percent by weight) and sodium dichloro-s-triazinetrione (sodium dichioro- isocyanurate). Class 2: barium bromate, barium chlorate, barium hypochlorite, barium perchlorate, barium perrnanga- 3a0 2003 INTERNATIONAL FIRE CODE® nate, 1-bromo-3-chloro-5, 5-dimethylhydantoin, cal- ciumchlorate, calcium chlorite, calcium hypochlorite (50 percent or less by weight), calcium perchlorate, calcium permanganate, chromium trioxide (chromic acid), copper chlorate, balane (1, 3-dichloro-5, 5-dimethythydantoin), hydrogen peroxide (greater than 27.5 percent up to 52 percent), lead perchlorate, lithium chlorate, lithium hypochlorite (more than 39 percent available chlorine), lithium perchlorate, mag- nesium bromate, magnesium chlorate, magnesium perchlorate, mercurous chlorate, nitric acid (more than 40 percent but less than 86 percent), perchloric acid solutions (more than 50 percent but less than 60 percent), potassium perchlorate, potassium per- manganate, potassium peroxide, potassium superoxide, silver peroxide, sodium chlorite (40 per- cent or less by weight), sodium perchlorate, sodium perchlorate monohydrate, sodium permanganate, so- dium peroxide, strontium chlorate, strontium per- chlorate, thallium chlorate, Iriehloro-s-tdazmehione (tdehlomisoeyanudc acid), area hydrogen peroxide, zinc bromate, zinc chlorate and zinc peananganate. Clas"s 1: all inorganic nitrates (unless otherwise classi- fied), all inorganic nitrites (unless otherwise classi- fied), ammonium persulfate, barium peroxide, calcium peroxide, hydrogen peroxide solutions (greater than 8 percent up to 27.5 percent), lead diox- ide, lithium hypochlorite (39 percent or less available chlorine), lithium peroxide, magnesium peroxide, manganese dioxide, nitric acid (40 percent concentra- tion or less), perehloric acid solutions (less than 50 Worst by weight), potassium dichromate, potassium percarbonate, potassium persulfate, sodium carbon- ate peroxide, sodium dichloro-s-triazinettione dihydrate, sodium dichromate, sodium perborate (an- hydrous), sodium perborate monohydrate, sodium perborate tetrahydrate, sodium percarbonate, sodium persulfate, strontium peroxide and zinc peroxide. E102.1.8 Organic peroxides. Organic peroxides contain the double oxygen or peroxy (-o-o) group. Some are flazn- mable compounds and subject in explosive decomposition. They are available as: 1. Liquids. 2. Pastes. 3. Solids (usually finely divided powers). E102.1.8.1 Classification of organic peroxides ac- cording to hazard. Unclassified: Unclassified organic peroxides are ca- pable of detonation and are regulated in accordance with Chapter 33. Class I: acetyl cyclohexane sulfonyl 60-65 percent concentration by weight, fulf ntyl peroxide, benzoyl peroxide over 98 percent concentration, t -butyl hydroperoxide 90 percent, t -butyl peroxyacetate 75 percent, t -butyl peroxyisepropylcarbonate 92 per- cent, diisopropyl peroxydicarbonate 100 percent, APPENDIX E di -n -propyl peroxydicarbonate 98 percent, and di -n -propyl poroxydicarbtmate 85 percent. Class II: acetyl peroxide 25 percent, t -butyl hydroperoxide 70 percent (with D1BP and t-BUGH diluents), t -butyl peroxybenzoate 98 percent, t -butyl peroxy-2-ethylhexanoate 97 percent, t -butyl peroxyisobutyrate 75 percent, t -butyl peroxy- isopropyl-carbonate 75 percent, t -butyl peroxypi- valate 75 percent, dybenzoyl peroxydicarbonate 85 percent, di -sec -butyl peroxydicarbonate 98 percent, di -sec -butyl peroxydicarbonate 75 percent, 1,1.-di-(t-butylperoxy)-3,5,5-trimethyecyelohexane 95 percent, di-(2-ethythexyl) peroxydicarbonate 97 percent, 2,5-dymethyl-2-5 di (benzoylperoxy) hex- ane 92 percent, and peroxyacetic acid 43 percent. Class III: acetyl cyclohexane sulfonal peroxide 29 percent, ben oylperoxide 78 percent, benzoylperox- ide paste 55 percent, benzoyl peroxide paste 50 per- cent peroxide/50 percent butylbenzylphthalate diluent, cumene hydroperoxide 86 percent, di-(4-butyleyclohexyl) peroxydicarbonate 98 per- cent, t -butyl peroxy-2-ethylhexanoate 97 percent, t -butyl peroxyneodecanoate 75 percent, decznoyi peroxide 98.5 percent, di -t -butyl peroxide 99 percent, 1,1-di-(t-butylperoxy)3,5,5-tdmethylcyclohexane 75 percent, 2,4-dichlorobenzoyl peroxide 50 percent, diisopropyl peroxydicarbonate 30 percent, 2,-5-dimethyl-2,5-di-(2-ethylhexanolyperoxy)-hex- ane 90 percent, 2,5-dimethyl-2,5-di-(t-butylperoxy) hexane 90 percent and methyl ethyl ketoneperoxide9 percent active oxygen diluted in dimethyl phthalate. Class IV: benzoyl peroxide 70 percent, benzoyl per- oxide paste 50 percent peroxide/l5 percent water/35 percent butylphthalate diluent, benzoyl peroxide slurry 40 percent, benzoyl peroxide powder 35 per- cent, t -butyl hydroperoxide 70 percent, (with water diluent), t -butyl peroxy-2-ethylhexanoate 50 percent, decumyl peroxide 98 percent, di-(2-ethylhexap peroxydicarMnate40percent, laurel peroxide 98 per- cent, p-medame hydroperoxide 52.5 percent, methyl ethyl ketone peroxide 5.5 percent active oxygen and methyl ethyl ketone peroxide 9 percent active oxygen diluted in water and glycols. Class V. benzoyl peroxide 35 percent, 1,1 -di -t -butyl peroxy 3,5,5-trimethylcyclohexane 40 percent, 2,5 -di -(t -butyl peroxy) hexane 47 percent and 2,4-pentenedione peroxide 4 percent active oxygen. E102.1.9 Pyrophoric materials. Examples include: 1. Oases: diborane, phosphine, silane. 2. Liquids: diethylaluminum chloride, di- ethylberyllium, diethylphosphine, diethylzinc, dimethylarsine, triethylaluminum etherate, tri- ethylbismuthine, triethylboron, trimethylalummum, trimethylgallium. 3. Solids: cesium, bafnium, lithium, white or yellow phosphorous, plutonium, potassium, rubidium, so- dium, thodum. 2003 INTERNATIONAL FIRE CODE® $81 APPENDIX E E102.1.10 Unstable (reactive) materials. Examples in- clude: Class 4: acetyl peroxide, dibutyl peroxide, dinumben- zene, ethyl nitrate, peroxyacetic acid and picric acid (dry) trinitrobenzene. Class 3: hydrogen peroxide (greater than 52 percent), hydroxylamine, nitromethane, paramtroaniline, perchloric acid and tetrafluorcethylene monomer. Class 2: acrolein, acrylic acid, hydrazine, metbacrylie acid, sodium perchlorate, styrene and vinyl acetate. Gass 1: acetic acid, hydrogen peroxide 35 percent to 52 percent, paraldehyde and tenahydrofumn. E102.1.11 Water -reactive materials. Examples include: Class 3: aluminum alkyls such as triethylaluminum, isola tylalummum and trimethylaluminum; bromine pentafluoride, bromine trifluoride, chlorodiethy4 aluminium and diethylzinc. Class 2: calcium carbide, calcium metal, cyanogen bro- mide, lithium hydride, methyldichlorosilane, potassium metal, potassium peroxide, sodi mameWl, sodium perox- ide, sulfuric acid and trichlorosilane. Class 1: acetic anhydride, sodium hydroxide, sulfur monochloride and titanium tetrachloride. E102.1.12 Cryogenic Raids. The cryogenics listed will ex- ist as compressed gases when they are stored at ambient temperatures. I. Flammable: carbon monoxide, deuterium (heavy hy- drogen), ethylene, hydrogen, methane. 2. Oxidizing. fluorine, nitric oxide, oxygen. 3. Corrosive: fluorine, nitric oxide. 4. Inert (chemically unreactive): argon, helium, kryp- ton, neon, nitrogen, xenon. 5. Highly toxic: fluorine, nitric oxide. E102.2 Health hazards. Materials classified in this section pose a health hazard. E102.2.1 Ifighly toxic materials. Examples include: I. Gases: aralne,cyanogen, diborane, fluorine, germane, hydrogen cyanide, nitric oxide, nitrogen dioxide, ozone, phosphine, hydrogen selenide, stibine. 2. liquids: acrolein, acrylic acid, 2-chloroethanol (eth- ylene chlorohydrin), hydrazine, hydrocyanic acid, 2-methylaziridine (propylenimine), 2-methyl- acemnitrile (acetone cyanohydrin), methyl ester isoeyanic acid (methyl isocyanate), nicotine, tetranitromethane and tetraethylstannane (tetraethyhin). 3. Solids: (aceto) phenylmercury (phenyl mercuric ace- tate),4-amompyrieine,arsenic pentoxide,arsenic tri- oxide, calcium cyanide, 2 -chloroacetophenone, aflatoxin B, decabonne(14), mercury (II) bromide (mercuric bromide), mercury (R) chloride (corrosive mercury chloride), pentachlorophenol, methyl para- thion, phosphorus (white) and sodium azide. E102.2.2 Toxic materials. Examples include: L Gases: boron trichloride, boron trifluoride, chlorine, chlorine trifluoride, hydrogen fluoride, hydrogen sul- fide, phosgene, silicon unraflusride. 2. Liquids: acrylonitrile, allyl alcohol, alpha-chlorotoluene, aniline, 1-chloro- 2,3-epoxypropane, chbmformic acid (allyl ester), 3-chloropropene (allyl chloride), o -cresol, crotonaldehyde, dibromomethane, diisopropylamine, diethyl ester sulfuric acid, dimethyl ester sulfuric acid, 2-frraldebyde (furfurol), furfural alcohol, phos- phorus chloride, phosphoryl chloride (phosphorus oxychloride) and thionyl chloride. 3. Solids: acrylamide, barium chloride, barium (II) ni- trate,benzidine,p-benzoquinone, beryllium chloride, cadmium chloride, cadmium oxide, chloroacetic acid, chlorophenylmercury (phenyl mercuric chloride), chromium (VI) oxide (chromic acid, solid), 2,4- dinitrotoluene, hydroquinone, memory chloride (cal- omel), mercury (R) sulfate (mercuric sulfate), os- mium tetroxide, oxalic acid, phenol, P-phenylenediamine, phenylhydrazine, 4-pbenyl- morpholine, phosphorus sulfide, potassium fluoride, potassium hydroxide, selenium (IV) disulfide and so - drum fluoride. E102.2.3 Corrosives. Examples include 1. Acids: Examples: chromic, formic, hydrochloric (muriatic) greater than 15 percent, hydrofluoac, nitric (greater than 6 percent, perchlorie, sulfuric (4 percent or more). 2. Bases (alkalis): hydroxides—ammonium (greater than 10 percent), calcium, potassium (greater than 1 percent), sodium (greater than I percent); certain car- bonates—potassium. 3. Other corrosives: bromine, chlorine, fluorine, iodine, ammonia Note: Corrosives that are oxidizers, e.g., nitric acid, chlorine, fluorine; or are compressed gases, e.g., ammo nia, chlorine, fluorine; or are water -reactive, e.g., con- centrated sulfuric acid, sodium hydroxide, are physical hazards in addition to being health hazards. SECTION E103 EVALUATION OF HAZARDS E103.1 Degree of hazard. The degree of hazard present de- pends on many variables which should be considered individu- ally and in combination. Some of these variables are as shown in Sections E103.1.1 through E103.1.5. E103.1.1 Chemical properties of the material. Chemical properties of the material determine self reactions and reao- tions which may occur with other materials. Generally, ma- terials within subdivisions of hazard categories will exhibit similar chemical properties. However, materials with simi- In chemical properties may pose very different hazards. 382 2003 INTERNATIONAL FIRE CODE® Each individual material should be researched to determine its hazardous propwrties and then considered in relation to other materials that it might contact and the surrounding en- vironment. E103.1.2 Physical properties of the material. Physical properties, such as whether a material is asolid, liquid or gas at ordinary temperatures and pressures, considered along with chemical properties will determine requirements for containment of the material. Specific gravity (weight of a liquid compared to water) and vapor density (weight of gas compared to air) are both physical properties which me im- portant in evaluating the hazards of a material. E103.1.3 Amount and concentration ofthematerial. The amount of material present and its concentration must be considered along with physical and chemical properties to determine the magnitude of the hazard. Hydrogen peroxide, for example, is used as an antiseptic and a hair bleach in low concentrations (approximately 8 percent in water solution). Over 8 percent, hydrogen peroxide is classed as art oxidizer and is toxic. Above 90 percent, it is a Class 4 oxidizer "that can undergo an explosive reaction when catalyzed or ex- posed toheat, shock or friction," a definition which inciden- tally also places hydrogen peroxide over 90 -percent concentration in the unstable (reactive) category. Small amounts at high concentrations may present a greater hazard than large amounts at low concentrations. E103.13.1 Mixtures. Gases—toxic and highly toxic gases include those gases which have an LCs, of 2,000 puts per million (ppm) or less when rets me exposed for a period of I hour or less. To maintain consistency with the definitions for these materials, exposure data for peri- ods other than 1 hour most be normalized to I hour. To classify mixtures of compressed gases thatcomain one or more toxic or highly toxic components, the LC, of the morme must be determined. Mixtures that contain only two components are binary mixtures. Those that contain more than two components are multi-component mix- tures. When two or more hazardous substances (compo- nents) having an LC,, below 2,000 ppm are present in a mixture, their combined effect, rather than that of the in- dividual substances (components), must be considered. In the absence of information to the contrary, the effects of the hazards present must be considered as additive. Excepfionsto the above tole may be made when there is a good reason to believe that the principal effects of the dif- ferent harmful substances (components) are not additive. For binary mixtures where the hazardous component is diluted with a nontoxic gas such as an inert gas, the LC,, of the mixture is estimated by use of the following formula: 1 LCs„ _ [C, l LCS, ] (Equation E-1) APPENDIX E For multi-component mixtures where more than one component has a listed LC, the LCs of the mixture is es- timated by use of the following formula: C_ 1 sm ILC +-(C,, ILC sa z sms)-s) (Equation E-2) where: LC",,, = LCsofthemixtureinpartspermillion(ppm). C, = concentration of component (i) in decimal percent. The concentration of the individual components in a mixture of gases is to be ex- pressed in terms of percent by volume. LC,a = LC,, of component (r). The LC,, of the com- ponent is based on a I -hour exposure. LCs data which are for other than I -hour exposures shall be normalized to 1 -hour by multiplying the LCy, for the time determined by the factor indicated in Table E103.1.3.1. The preferred mammalian species for LCs, data is the rat, as specified in the definitions of toxic and highly toxic in Chapter 2 of the international Fire Code. If data for rats are unavailable, and in the absence of information m the contrary, data for other species may be utilized. The data shall be taken in the following order of preference: rat, mouse, rabbit, guineapig, cat, dog, monkey. I, = component 1, component 2 and so on to the nth component. Examples: a. What is the LCso of a mixture of 15 -percent chlo- rine, 85 -percent nitrogen? The I -hour (rat)LCSsofpure chlorine is 293 ppm. LC, = 1/(0.15/293)or1.953ppm.Therefore, the mixture is toxic. b. What is the LCs, of a mixture of 15 -percent chlo- rine, 15 -percent fluorine and 70 -percent nitrogen? The 1 -hour (rat) LCs of chlorine is 293 ppm. The i -hour (rat) LCs of fluorine is 185 ppm LC, = 1 / (0.15 / 293) + (0.15 / 185) or 755 ppm. Therefore the mixture is toxic. c. Is the mixture of I percent phosphine in argon toxic or highly toxic? The 1 -hour (ret) LC, is 11 ppm. LCS,., = 1 / [0.0t / (17 2)] or 2,200 ppm. There- fore the mixture is neither toxic nor highly toxic. Note that the 4 -hour LCs of 11 ppm was normalized to 1 -hour by use of E103.1.3. I. 2003 INTERNATIONAL FINE CODE® 383 APPENDIX E TABLE E103.1.3.1 NORMALIZATION FACTOR TIME ansa) _— 0,5 —' MULTIPLY BY 0.7 1,0 1.0 _ 15 _ 1.2 20 3-0 1A 1.7 ad 5.0 0 22 _ 60 2.4 To 26 8,0 2.8 EULLIA Actual use, activity or process involving the material. The definition of handling, storage and use in closed systems refers to materials in packages orcontainers. Dispensing and use in open containers or systems describes situations where a material is exposed to ambient conditions or vapors are liberated to the atmosphere. Dispensing and use in open systems, then, are generally more hazardous sit- uations than handling, storage or use in closed systems. The actual use or process may include heating, electric or other sparks, catalytic or reactive materials and many other fac- tors which could affect the hazard and must therefore be thoroughly analyzed. E103.1.5 Surrounding conditions. Conditions such as other materials or processes in the area, type of construction of the structure, fire protection features (e.g., fire walls, sprinkler systems, alarms, etc.), occupancy (use) of adjoin- ing areas, normal temperatures, exposure to weather, etc., must be taken into account in evaluating the mound, E103.2 Evaluation questions. The following are sample eval- uation questions: L What is the material? Correct identification is important; exact spelling is vital. Check labels, MSDS, ask respon- sible persons, etc. 2. What are the concentration and strength? 3. What is the physical form of the material? Liquids, gases and finely divided solids have differing requirements for spill and leak control and containment. 4. How much material is present? Consider in relation to permit amounts, maximum allowable quantity per con- trol area (from Group H occupancy requirements), amounts which require detached storage and overall magnitude of the hazard. 5. What other matorials (including furniture, equipment and building components) are close enough to interact with the material? 6. What are the likely reactions? 7. What is the activity involving the material? S. Glow does the activity impact the hazardous chmaemris- tics of the material? Consider vapors released or hazards otherwise exposed. 9. What must the material be protected from? Consider other materials, temperature, shock, pressure, etc. 10. Whateffects of the material must people and the environ- ment be protected from? 11. How can protection be accomplished? Consider: 11.1, Proper containers and equipment. 11.2. Separation by distance or construction. 11.3. Enclosure in cabinets or rooms. 11.4- Spill control, drainage and containment. 11.5. Control systems — ventilation, special elecm- cal, detection and alarm, extinguishment, ex- plosion venting, limit controls, exhaust scrubbers and excess flow control. 11.6. Administrative (operational) controls—signs, ignition source control, security, personnel training, established procedures, storage plans and emergency plans. Evaluation of the hazard is a strongly subjec- tive process; therefore, the person charged with this responsibility must gather as much relevant data as possible so that the decision will be ob- jective and within the limits prescribed in laws, policies and standards. It may be necessary to cause the responsible persons in charge to have tests made by quali- fied persons or testing laboratories to support contentions that a particular material or process is or is not hazardous. See Seeman 104.7.2 of the International Fire Code. 384 2003 INTERNATIONAL FIRE CODES The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. SECTION F101 GENERAL F101.1 Scope. Assignment of levels of hazards to be applied to specific hazard classes as required by NFPA 704 shall be in ac- cordance with this appernix.Tbeappendix isbased onapplies- tion of the degrees of hazard as defined in NFPA 704 arranged by hazard class as for specific categories defined in Chapter 2 of the International Fire Code and used throughout. F101.2 General. The hazard rankings shown in Table F101.2 have been established by using guidelines found within NFPA 704. As noted in Section 1-5 of NFPA 704, there could be spe- cificreasons to alter the degree of hazard assigned to a specific material; for example, ignition temperature, flammable range or susceptibility of a container to rupture by an internal com- bustion explosion or to metal failure while under pressure or because of heat from external fire. As a result, the degree of hazard assigned for the same material can vary when assessed by different people of equal competence. The hazard rankings assigned to eachelass represent mason - able minimum hazard levels for a given class based on the use of criteria established by NFPA 704. Specific cases of use or storage may dictate the use of higher degrees of hazard in cer- tain cases. SECTION F102 REFERENCED STANDARDS ICC IAC International Fire Code 17101.1 Idenfi&ationofthe NFPA 704 Hazards of Materials for F101.1, F101.2 Emergency Response 2003 INTERNATIONAL FIRE CODE® 385 w y TABLE F101.2 FIRE FIGHTER WARNING PLACARD DESIGNATIONS BASED ON HAZARD CLASSIFICATION CATEGORIES HAZARD CATEGORY DESIGNATION Combustible liquid 11 F2 Combustible liquid IIIA F2 Combustible liquid HIS Fl Combustible dust F4 Combostible fiber F3 Cryogenic flammable F4, H3 Cryogenic oxidizing OX, H3 Explosive R4 Flammable solid F2 Flammable gas (gaseous) F4 Flammable gas (lique(bed) F4 Flammable liquid IA F4 Flammable liquid IR F3 Flammable liquid IC F3 Orgaoie peroxide, UD R4 Organic peroxide 1 F4, R3 Organic peroxide lI F3, R3 Organic peroxide 111 F2, R2 Organic peroxi&IV Fl, RI Organic peroxide V Nonhazard Oxidizing gas (gaseous) OX Oxidizing gas (liquefied) OX Oxidieer4 OX McIver 3 OX Oxidizer 2 OX Pyrophorle gases F4 Pyrophoric solids, liquids F3 Unstablereactive4D R4 Unstable rwctive 3D R4 I)nsmble re active 3N 123 Unstable reactive 2 R2 Water teaci ve 3 W, R3 Water reactive 2 W, R2 Corrosive H3, COR Toxic H3 Iffighly toxic I H4 F....Flammablep[egory. COR --Center", R—Reavowe c.s,ge, UD—Uvclasslfied damnable material. H—RaNlh category. 4D --Class 4 deumable material. W—Special hazard: water reactive. 31)—Cixss 3 detonable material. OX-Specialhazardoximzm,pm,o s. 3N --(Mase 3 noaduonable material, 308 2003 INTERNATIONAL FIRE CODE® APPENDIX G CRYOGENIC FLUIDS -WEIGHT AND VOLUME EQUIVALENTS The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. SECTION G101 GENERAL G101.1 Stripe. This appendix is used to convert from liquid to gas for cryogenic fluids. G101.2 Conversion. Table 6101.2 shall be used to determine the equivalent amounts of cryogenic fluids in either the liquid or gas phase. G101.2.1 Use of the table. To use Table 6101.2, read hori- act ally across the line of interest. For example, to deter- mine the number of cubic feet of gas contained in 1.0 gallon (3.785 L) of liquid argon, find 1.000 in the column entitled `Volume of Liquid at Normal Roiling Point" Reading across the line under the column entitled' Volume of Gas at 70°F and 1 atmosphere 14.7 psis'the value of 112.45 cubic feet (3184 m') is found. G101.2.2 Other quantities. If other quantities are of inter- est, the numbers obtained can be multiplied ordivided to ob- tain the quantity of interest. For example, to determine the number of cubic feet of argon gas contained in a volume of 1,000 gallons (3785 L) of liquid argon at its normal boiling point, multiply 112.45 by 1,000 to obtain 112,450 cubic fact (3184 m'). 2003 INTERNATIONAL FIRE CODE® 387 APPENDIX G TABLE 6101.2 WEIGHT AND VOLUME EOUIVALENTS FOR COMMON CRYOGENIC FLUIDS' Ru SL 1 pound =0.454 kg, I gallon = 3.785 L, I cubic fool =0.02832 m3, -C = I('F)-321/1.8,1 Jenna pef square inch am esphem =6.895 kPa. a Thevalues lilted lot trquedled wmal gar (LNG) me"typicaCbalues. LNG es a mlxuue of hydmcarbnn gmes, and no two LNG streams have exactly the rame composition. 306 2003 INTERNATIONAL FIRE CODE® VOLUME OF LIQUID AT NORMAL VOLUME OF GAS AT INLF AND WEIGHT OF LIQUID OR GAS BOILING POINT 1 ATMOSPHERE 10.7 PSM CRYOGENIC FLUID Pcnmd. Kilogmat. LRen Gitlin. Cubic teat Cubi[mBiere 1.000 0.454 (326 0.086 9.67 0.274 2.205 1.000 0,718 0.190 21.32 0.604 3.072 1.393 1.000 0264 29.71 0.841 A[gon 11.628 5.274 3.785 1.000 112.45 3.184 10,340 4.690 3.366 0.889 100.00 2832 3.652 1,656 1.189 0.314 35.31 1,000 1.000 0.454 3.631 0,959 9672 2.739 1205 1.000 8,006 2.115 21323 6.038 0,275 0.125 1.000 0264 26,63 0.754 Helium 1,042 0.473 3,785 1.000 100.82 2855 1.034 0A69 3.754 0.992 HKLoo 2.832 0365 0.166 1.326 0350 35.31 1.000 1000 0A54 6.409 1.693 19196 5,436 2.205 1000 14.130 3,733 423.20 11.984 0.156 0.1071 1.000 0.264 29.95 0.848 Hydrogen 0.591 0.268 3.785 1.000 113.37 3210 0.521 0.236 3,339 0.882 100.(X) 2.832 0.184 0.083 1179 0.311 35.31 1.000 IAN) 0.454 0.397 0.105 1200 0.342 2.205 1.000 0.876 0.231 26.62 0.754 2.517 1.142 1.010 0.264 30.39 0.861 Oxygen 9.527 4.321 3.785 1.000 115.05 3.250 8,281 3.756 3.290 0.869 100.00 2.832 2.924 1.327 1.162 0.307 35.31 1.000 1.000 0A54 0.561 0.148 13.80 0.391 1205 1.000 1.237 0,327 30.43 0.862 1.782 0.808 1,000 0.264 24.60 0.697 Nitrogen 6.746 3.060 3785 L000 93.11 2.637 7.245 3.286 L065 1.074 100.00 2.832 2558 1,160 1.436 0379 35.31 L Mw 0.454 1,052 0,278 22968 0,650 2205, 1.000 2.320 0,613 50,646 1/134 0.951 0.431 1,000 0.264 21.812 0618 LNG 3.600 1.633 3.785 1.000 82.62 2.340 4356 1.976 4.580 1.210 100.00 2.832 11.501 5.217 1.616 0,427 35.31 L000 Ru SL 1 pound =0.454 kg, I gallon = 3.785 L, I cubic fool =0.02832 m3, -C = I('F)-321/1.8,1 Jenna pef square inch am esphem =6.895 kPa. a Thevalues lilted lot trquedled wmal gar (LNG) me"typicaCbalues. LNG es a mlxuue of hydmcarbnn gmes, and no two LNG streams have exactly the rame composition. 306 2003 INTERNATIONAL FIRE CODE® ';�lT�c# lilma r `8 " FEE SCHEDULES FOR NEW COMMERCIAL PROJECTS: These fees may be assessed with the application submittal: BUILDING PERMIT FEE. BUILDING AND MEP PLAN REVIEW FEE. FUZE PLAN REVIEW FEE. PLUMBING FEE MECHANICAL FEE. ELECTRICAL FEE. HEALTH FEE (IF APPLICABLE). METER FEE & SANITARY SEWER FEES. IMPACT FEE. - $7.50 per $1000 valuation of work Minimum $20.00. $.07 per square foot of building area • $.02 per square foot of building area ranging from 0-100,000 square feet For buildings over 100,000 square feet, please refer to fee schedules. MECHANICAL, ELECTRICAL, AND PLUMBING FEES: These fees are calculated by square footage of floor area 1-3,000 square feet $60.00 3,00f-10,000 square feet $80.00 10,001-50,000 square feet $100.00 50,001-100,000 square feet- $125.00 over 100,000 square feet $150.00 Fees are separate (i.e. $60.00 plumbing, $60.00 electrical, $60.00 mechanical. $250.00 (If applicable to requirements.) Or INNUMMAiM 2:114-1 Please contact the City of Anna Public Works Department for meter and sanitary sewer sizes Verify that water and sewer taps exist on site. - Fees will be paid to the City of Anna Building Inspection Department. RVIPACT FEES: Please contact the City of Anna Building Inspection Department for all Impact fees. Fees willbe paid to the City of Aura Building Inspection Department When submitting application for Sbell only permit, include only shell valuation. When building bas more than one floor, separate permits per floor is required. This fee calculation is provided for information only. The City of Anna Building Inspections Department will calculate and assess all fees.